F498
Permanent Magnet (PM) Motor Constant 1
Program Motor PM Motor
This parameter is used with synchronous motor applications only.
Contact the TIC Customer Support Center for information on this parameter.
Permanent Magnet (PM) Motor Constant 2
Program Motor PM Motor
This parameter is used with synchronous motor applications only.
Contact the TIC Customer Support Center for information on this parameter.

Acceleration Time 2

Program Special  Acc/Dec 1 – 4 Settings
This parameter specifies the time in seconds for the output of the ASD to go
from 0.0 Hz to the Maximum Frequency for the 2 Acceleration profile. The
Accel/Decel pattern may be set using F502. The minimum Accel/Decel time
may be set using F508.
This setting is also used to determine the acceleration rate of the UP/DOWN
Frequency Functions.
Note:
An acceleration time shorter than the load will allow may cause
nuisance tripping and mechanical stress to loads. Automatic
Accel/Decel, Stall, and Ridethrough settings may lengthen the
acceleration times.

Deceleration Time 2

Program Fundamental Accel/Decel 1 Settings
This parameter specifies the time in seconds for the output of the ASD to go
from the Maximum Frequency to 0.0 Hz for the 2 Deceleration profile. The
Accel/Decel pattern may be set using F502. The minimum Accel/Decel time
may be set using F508.
This setting is also used to determine the deceleration rate of the UP/DOWN
Frequency Functions.
Note:
A deceleration time shorter than the load will allow may cause
nuisance tripping and mechanical stress to loads. Automatic
Accel/Decel, Stall, and Ridethrough settings may lengthen the
deceleration times.
164
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Direct Access Number — F498
Parameter Type — Numerical
Factory Default — (ASD-Dependent)
Changeable During Run — Yes
Minimum — 0
Maximum — 100
Units — %
Direct Access Number — F499
Parameter Type — Numerical
Factory Default — (ASD-Dependent)
Changeable During Run — Yes
Minimum — 0
Maximum — 100
Units — %
Direct Access Number — F500
Parameter Type — Numerical
Factory Default — (ASD-Dependent)
Changeable During Run — Yes
Minimum — 0.1
Maximum — 6000.0
Units — Seconds
Direct Access Number — F501
Parameter Type — Numerical
Factory Default — (ASD-Dependent)
Changeable During Run — Yes
Minimum — 0.1
Maximum — 6000
Units — Seconds
H9 ASD Installation and Operation Manual