F447

Regenerative Braking Torque Limit 3 Level

Program Torque Manual Torque Limit Settings
This parameter is used to set the negative torque upper-limit for the 3 motor
profile when multiple motors are controlled by a single drive or when a single
motor is to be controlled by multiple profiles.
Power Running Torque Limit 4 Level
Program Torque Manual Torque Limit Settings
This parameter is used to set the positive torque upper-limit for the 4 motor
profile when multiple motors are controlled by a single drive or when a single
motor is to be controlled by multiple profiles.

Regenerative Braking Torque Limit 4 Level

Program Torque Manual Torque Limit Settings
This parameter is used to set the negative torque upper-limit for the 4 motor
profile when multiple motors are controlled by a single drive or when a single
motor is to be controlled by multiple profiles.

Accel/Decel Operation After Torque Limit

Program Torque Torque Limit Settings
In a Crane/Hoist application that is operating using a mechanical brake, this
parameter is used to minimize the delay between the brake release and the
output torque reaching a level that can sustain the load.
This setting may reference time or the operating speed of the motor.
Settings:
0 — In Sync with Accel/Decel
1 — In Sync with Minimum Time

Power Running Stall Continuous Trip Detection Time

Program Protection Stall
This parameter is used to extend the Over-Voltage Stall (F305) and the Over-
Current Stall (F017) time settings.
H9 ASD Installation and Operation Manual
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Direct Access Number — F447
Parameter Type — Numerical
Factory Default — 250.0 (Disabled)
Changeable During Run — Yes
Minimum — 0.00
Maximum — 250.0 (Disabled)
Units — %
Direct Access Number — F448
Parameter Type — Numerical
Factory Default — 250.0 (Disabled)
Changeable During Run — Yes
Minimum — 0.00
Maximum — 250.0 (Disabled)
Units — %
Direct Access Number — F449
Parameter Type — Numerical
Factory Default — 250.0 (Disabled)
Changeable During Run — Yes
Minimum — 0.00
Maximum — 250.0 (Disabled)
Units — %
Direct Access Number — F451
Parameter Type — Selection List
Factory Default — In Sync with Accel/
Decel
Changeable During Run — Yes
Direct Access Number — F452
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 1.0
Units — Seconds