F371
PID Output Lower-Limit
Program Feedback Feedback Settings
Selecting Speed PID at parameter
function as the Lower-Limit while operating in the PID Control mode.
Process Increasing Rate
Program Feedback Feedback Settings
This parameter is used to limit the rate that the output of the ASD may increase
for a given difference in the speed reference and the PID feedback value.
Process Decreasing Rate
Program Feedback Feedback Settings
This parameter is used to limit the rate that the output of the ASD may decrease
for a given difference in the speed reference and the PID feedback value.
Number of PG Input Pulses
Program Feedback PG Settings
This parameter is used to set the number of pulses output from a shaft-mounted
encoder that is used to indicate one revolution of rotation (360°) of the motor or
of the motor-driven equipment.
Number of PG Input Phases
Program Feedback PG Settings
This parameter determines the type of information that is supplied by the phase
encoder.
Settings:
1 — Single Phase
2 — Two Phase
150
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
F359
allows for this parameter setting to
Direct Access Number — F371
Parameter Type — Numerical
Factory Default — 4.00
Changeable During Run — Yes
Minimum — Lower-Limit (F013)
Maximum — Upper-Limit (F012)
Units — Hz
Direct Access Number — F372
Parameter Type — Numerical
Factory Default — 10.0
Changeable During Run — Yes
Minimum — 0.1
Maximum — 600.0
Units — Seconds
Direct Access Number — F373
Parameter Type — Numerical
Factory Default — 10.0
Changeable During Run — Yes
Minimum — 0.1
Maximum — 600.0
Units — Seconds
Direct Access Number — F375
Parameter Type — Numerical
Factory Default — (ASD-Dependent)
Changeable During Run — No
Minimum — 12
Maximum — 9999
Direct Access Number — F376
Parameter Type — Selection List
Factory Default — (ASD-Dependent)
Changeable During Run — Yes
H9 ASD Installation and Operation Manual
F376