F686
AM Bias Adjustment
Program Terminal Analog Output Terminals
This parameter setting is used to ensure that a zero-level input signal produces a
zero-level output at the AM terminal.
Set the function set at
proper operation.
See
F670
for more information on this setting.
MON 1 Voltage/Current Output Switching
Program Terminal Analog Output Terminals
This parameter is used to set the output signal type of the MON1 output
terminal.
Settings
0 — -10 V – +10 V
1 — 0 – 10 V
2 — 0 – 20 mA
MON 1 Output Gradient Characteristic
Program Terminal Analog Output Terminals
This parameter sets the output response polarity of the MON1 output terminal.
The MON1 output terminal response may be set to respond inversely (-) or
directly (+) to the input signal.
See parameter
F672
for more information on this setting.
Settings:
0 — Minus (Negative Gradient)
1 — Plus (Positive Gradient)
MON 1 Bias Adjustment
Program Terminal Analog Output Terminals
This parameter setting is used to ensure that a zero-level input signal produces a
zero-level output at the MON1 terminal.
Set the assigned function of parameter
to a zero output.
See parameter
F672
for more information on this setting.
MON 2 Voltage/Current Output Switching
Program Terminal Analog Output Terminals
This parameter is used to set the output signal type of the MON2 output
terminal.
See parameter
F674
for more information on this setting.
Settings
0 — -10 V – +10 V
1 — 0 – 10 V
2 — 0 – 20 mA
H9 ASD Installation and Operation Manual
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
F670
to zero and then set this parameter to zero for
F672
to zero and then set this parameter
Direct Access Number — F686
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — -10.0
Maximum — +100.0
Units — %
Direct Access Number — F688
Parameter Type — Selection List
Factory Default — 0 – 10V
Changeable During Run — Yes
Direct Access Number — F689
Parameter Type — Selection List
Factory Default — Plus
Changeable During Run — Yes
Direct Access Number — F690
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — -10.0
Maximum — 100.0
Units — %
Direct Access Number — F691
Parameter Type — Selection List
Factory Default — 0 – 10V
Changeable During Run — Yes
F691
195