Standard System Installation
6.
Check each UPS front panel display for active alarms or notices (other than "Batteries Disconnected").
Resolve any active alarms before continuing. See "Troubleshooting" on page 135.
7 .
Switch all UPS battery circuit breakers to the ON (
8.
If optional EBMs are installed, switch all EBM battery circuit breakers to the ON (
9.
Verify that the "Batteries Disconnected" alarm on each UPS has cleared. Verify that no other alarms
appear on any UPS front panel display.
If an
from the front panel to view the active alarms. Correct the alarms and restart if necessary.
10. On any UPS, press any button on the front panel display to activate the menu options, and then press
the button until the TURN UPS ON/OFF menu displays.
11. Press the
12. Confirm the selection. Press and hold the
Verify that the
and any loads not connected through the load connector are now energized.
If the
from the front panel to view the active alarms. Correct the alarms and restart if necessary.
NOTE
Each UPS should be in Normal mode. By default, Normal mode operates on the High Efficiency setting
(see "Normal Mode" on page 97).
13. To energize loads connected through the load connectors, switch all load connector circuit breakers to the
ON (
14. On any UPS, press the
15. Verify that all UPSs in the parallel system are updated to the same firmware version.
NOTE
On each UPS, press any button on the front panel display to activate the menu options, and then press
the button until the IDENTIFICATION menu displays. Press the
data, including the firmware version.
If any firmware versions do not match, install the firmware from the supplied BladeUPS: Documents,
Firmware, and Installation Video CD or visit www.eaton.com/powerquality to download the latest version
and the instructions for installing it.
16. If optional EBMs are installed, see "Configuring the UPS for EBMs" on page 104 to set the number of
installed EBMs for each UPS.
86
Eaton BladeUPS 12 kVA to 60 kVA (N+1) User's Guide 164201649—Rev 7
indicator is flashing on any UPS, do not proceed until all alarms are clear. Check the UPS status
button to display the TURN SYSTEM ON option; press the
indicator illuminates solid on each UPS, indicating that the UPS is operating normally
indicator on any UPS is flashing, do not proceed until all alarms are clear. Check the UPS status
For a parallel-ready system (a single UPS installed to be part of a future parallel
system), set the Parallel Operation Settings / Parallel Operation Mode to "Capacity
Mode" to prevent unnecessary alarms (see Chapter 5, "Operation").
) position.
ESC
button until the Start screen appears.
Firmware v2.0 does not operate in a parallel system with v1.xx. All UPSs must have
firmware v2.x installed.
) position.
button for three seconds, until the UPS stops beeping.
button to display the identification
) position.
button.