Eaton bladeups User Manual page 134

Eaton bladeups 12 kva to 60 kva (n+1) systems
Hide thumbs Also See for bladeups:
Table of Contents

Advertisement

Specifications
Table 18. BladeUPS Bar
Dimensions (W D H)
Weight
UPS Connections
Rack Placement
Table 19. BladeUPS Module Rack
Dimensions (W x D x H)
Weight
Table 20. Electrical Input
Nominal Voltage
Nominal Frequency
Frequency Range
Default Frequency
Rated Input Current
Connections
Noise Filtering
Input Power Factor
Input Mode
126
Eaton BladeUPS 12 kVA to 60 kVA (N+1) User's Guide 164201649—Rev 7
BladeUPS Bar 4-High
152 145 1296 mm (6.0" x 5.7" 51.0")
BladeUPS Bar: 18.1 kg (40 lb)
Wireway enclosure: 20.4 kg (45 lb)
Total weight: 38.5 kg (85 lb)
Up to 4, using Anderson input/output connectors
Bottom wireway fits into the bottom 6U of standard rack space.
Top wireway fits into the top 6U of standard rack space.
Rack without side panels or casters: 99 kg (219 lb)
Side panels (each): 8.5 kg (19 lb); Casters (4): 5 kg (10 lb)
BladeUPS 12 Model
120/208V three-phase
50/60 Hz
45–65 Hz
Auto-detected
36A
IEC 309-60A power cord
For paralleling, a single Anderson input/output cord connects to the
Up to 6, using Anderson input/output connectors
610 1067 2032 mm (24" 42" 80")
Total weight: 121 kg (267 lb)
BladeUPS Bar (see Table 16 on page 125).
MOVs and common mode line filter
High Efficiency setting: load dependent
Standard setting: >0.99
Three-phase
BladeUPS Bar 6-High
152 145 1829 mm (6.0" 5.7" 72.0")
BladeUPS Bar: 24.5 kg (54 lb)
Wireway enclosure: 20.4 kg (45 lb)
Total weight: 44.9 kg (99 lb)
BladeUPS 12i Model
230/400V three-phase
50/60 Hz
45–65 Hz
Auto-detected
24A
IEC 309-32A power cord