Eaton bladeups User Manual page 129

Eaton bladeups 12 kva to 60 kva (n+1) systems
Hide thumbs Also See for bladeups:
Table of Contents

Advertisement

Electronics Module
Locking Screw
LCD Cable
Figure 83. Removing the UPS Front Cover and Electronics Module
4.
Label the original module with masking tape or some other identifier. Record the serial number of the
replacement module for your warranty.
If not returning the electronics module for warranty, see the following section, "Recycling the Used
Battery or UPS, " for proper disposal.
5.
Insert the replacement module by sliding it carefully into the cabinet. Verify that it seats firmly against the
rear of the cabinet.
Reinstall the electronics module locking screw.
6.
Parallel configurations only. Reconnect the redundant signal cable(s).
7 .
Replace the UPS front cover (see Figure 84):
Plug the LCD cable from the control panel on the front cover into the connector on the electronics
module. Use care to loop the LCD cable gently in front of the electronics module.
Push the top of the front cover firmly into place, and then push the bottom firmly into place.
8.
Verify that no alarms are indicated on the control panel.
9.
Transfer the UPS to Normal mode.
Ring Handle
Eaton BladeUPS 12 kVA to 60 kVA (N+1) User's Guide 164201649—Rev 7
UPS Maintenance
121