Eaton bladeups User Manual page 83

Eaton bladeups 12 kva to 60 kva (n+1) systems
Hide thumbs Also See for bladeups:
Table of Contents

Advertisement

Standalone/
Parallel
(remove)
For Parallel
Use Only
Redundant Signal Cable
Standalone/
Parallel
For Parallel
Use Only
Standalone/
Parallel
Figure 63. Typical CAN Bridge Card and Redundant Signal Wiring
13. Install a redundant signal cable between the For Parallel Use Only and Standalone/Parallel terminals on
each UPS as shown in Figure 63.
Be sure to check correct polarity when installing the cable.
If polarity or wiring is not correct, the parallel system does not operate normally. For example,
when shutting down one UPS, the remaining UPS transfers the load to bypass instead of
supporting the load. Verify that all wiring is correct for proper operation.
Blue Terminating Plug
Blue Terminating Plug
CAUTION
Eaton BladeUPS 12 kVA to 60 kVA (N+1) User's Guide 164201649—Rev 7
Standard System Installation
UPS 3
CAN
CAN
IN
OUT
UPS 2
CAN Bridge Card Cable
UPS 1
75

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents