Standard System Installation
4.
Unpack the Powerware Hot Sync CAN Bridge Card and verify that the card was not damaged during
shipment (see Figure 60).
Figure 60. Powerware Hot Sync CAN Bridge Card
5.
If there is a Jumper J7 on the Powerware Hot Sync CAN Bridge Card, remove and discard (see Figure 67
on page 84).
NOTE
6.
Remove the X-Slot communication bay cover on the UPS and retain the screws.
7 .
Loosely install the Powerware Hot Sync CAN Bridge Card into the open X-Slot communication bay on the
UPS rear panel.
8.
Repeat Steps 4 through 7 to install a CAN Bridge Card in each UPS to be paralleled.
NOTE
72
Eaton BladeUPS 12 kVA to 60 kVA (N+1) User's Guide 164201649—Rev 7
Eaton recommends installing the Powerware Hot Sync CAN Bridge Card in
X-Slot Communication Bay 2 (see Figure 59 on page 70), leaving Communication
Bay 1 available for other types of X-Slot cards.
The BladeUPS parallel system can automatically assign identities to each UPS in the
system based on the order in which their CAN Bridge Cards are wired in Steps 9
through 12. For more information, see "Auto-Identification" on page 113.