Eaton bladeups User Manual page 37

Eaton bladeups 12 kva to 60 kva (n+1) systems
Hide thumbs Also See for bladeups:
Table of Contents

Advertisement

3.
Remove the six screws on the conduit landing plate and retain. Remove the plate and retain.
See Figure 13.
Ferrite Assembly (mounted)
Conduit Landing Plate
Ferrite Assembly (mounted)
Figure 13. Removing the Conduit Landing Plate
4.
Use a Greenlee
punch to provide one or more holes in the conduit landing plate to accommodate the
®
input and output wiring from the utility to the BladeUPS Bar.
Replace the conduit landing plate.
Bottom Entry Rack
Top Entry Rack
Eaton BladeUPS 12 kVA to 60 kVA (N+1) User's Guide 164201649—Rev 7
Preassembled System Installation
29