Ups Maintenance; Ups And Battery Care; Storing The Ups And Batteries; When To Replace Batteries - Eaton bladeups User Manual

Eaton bladeups 12 kva to 60 kva (n+1) systems
Hide thumbs Also See for bladeups:
Table of Contents

Advertisement

Chapter 7

UPS Maintenance

This chapter explains how to:
Care for the UPS and batteries
l
Replace the UPS batteries and EBMs
l
Test new batteries
l
Replace the electronics module
l
Replace a UPS in a parallel system
l
Recycle used batteries or UPS
l
Update the UPS firmware
l

UPS and Battery Care

For the best preventive maintenance, keep the area around the UPS clean and dust-free. If the atmosphere is
very dusty, clean the outside of the system with a vacuum cleaner.
For full battery life, keep the UPS at an ambient temperature of 25°C (77°F).

Storing the UPS and Batteries

If you store the UPS for a long period, recharge the battery every 6 months by connecting the UPS to utility
power. The batteries charge to 80% capacity in fewer than 5 hours. However, Eaton recommends that the
batteries charge for 48 hours after long-term storage.
Check the battery recharge date on the shipping carton label. If the date has expired and the batteries were
never recharged, do not use the UPS. Contact your service representative.

When to Replace Batteries

When the
replacing. Contact your service representative to order new batteries.

Replacing Batteries

Batteries can be replaced easily without turning the UPS off or disconnecting the load.
If you prefer to remove input power to change the batteries, see "Individual Paralleled UPS Shutdown" on
page 102.
Consider all warnings, cautions, and notes before replacing batteries.
NOTE
The batteries in the UPS are rated for a 3–5 year service life. The length of service
life varies, depending on the frequency of usage and ambient temperature.
Batteries used beyond expected service life will often have severely reduced
runtimes. Replace batteries at least every 5 years to keep units running at peak
efficiency.
indicator flashes slowly and the audible alarm beeps intermittently, the batteries may need
NOTE
DO NOT DISCONNECT the batteries while the UPS is in Battery mode.
Eaton BladeUPS 12 kVA to 60 kVA (N+1) User's Guide 164201649—Rev 7
115