Programming the Panel

Alarm Settings

Alarm settings specify how the panel behaves during cer-
tain alarm situations. Alarm settings are global.
Alarm Messages Played at High Volume
Default = 1 (On)
Choose whether or not you want alarm messages (on voice siren)
always played at high volume. If not, they will be played at nor-
mal volume.
Note
Auxiliary/Medical alarm messages are never sounded at
high volume regardless of this setting.
To Set Alarm Message Volume:
1. Once the item number has been entered, enter 1 for on (high
volume), or 0 for off (normal volume).
2. Press # to apply the new setting.
Evacuation Messages
Default = 0 (Off)
Choose whether or not fire alarm evacuation audio messages are
played during fire alarms. If off, evacuation messages will not
play during fire alarms.
To Turn Evacuation Messages On/Off:
1. Once the item number has been entered, enter 1 for on, or 0
for off.
2. Press # to apply the new setting.
Evacuation Message Count
Default = 4 Messages
Set the number of evacuation messages (0–4) to be played. Evac-
uation messages are automatically played until the siren times
out, the alarm is silenced, or the alarm is canceled. This setting
determines the number of evacuation messages played starting
with number 1 and up (then repeated). For example, if set to 2,
evacuation messages 1 and 2 will be played and repeated.
Note
In order for the panel to play evacuation messages dur-
ing fire alarms, the Evacuation Messages setting
(17083) must be set to "on".
To Set Evacuation Message Count:
Once the item number has been entered, enter the evacuation
message count (0–4) and press #.
First Fire Alarm Disarm/Silence
Default = Off
When set to on, the first code entry will silence a fire alarm and
the second code entry will cancel the alarm. If off, the first code
entry will silence and cancel the alarm.
To Turn First Fire Alarm Disarm/Silence On/Off:
1. Once the item number has been entered, enter 1 for on, or 0
for off.
2. Press # to apply the new setting.
38
Unsilence Alarm
Default = 0 (Off)
Choose whether or not to enable unsilencing of alarm after silenc-
17079
ing period expires. If on, a silenced fire alarm will resound.
Note
The silencing period can be set using the Time Fire
Alarm is Silenced setting (17111) below.
To Turn Unsilence Alarm On/Off:
1. Once the item number has been entered, enter 1 for on, or 0
for off.
2. Press # to apply the new setting.
Time Fire Alarm is Silenced
Default = 30 Seconds
Specify the amount of time (in seconds), for which sirens are
silenced during a fire alarm (after a user enters a valid access
17083
code).
Note
The alarm will not unsilence if Unsilence Alarm setting
(17126) is set to off.
To Set Time Fire Alarm is Silenced:
1. Once the item number has been entered, specify the silence
time (15–999).
2. Press # to apply the new setting.
Annunciate Earliest Fire Alarm
17104
Default = 0 (Off)
If on, the panel will annunciate the earliest active fire alarm
instead of the most recent, during a multiple fire alarm situation.
Note
This option is intended for panels installed in Canada.
To Turn Annunciate Earliest Fire Alarm On/Off:
1. Once the item number has been entered, enter 1 for on, or 0
for off.
2. Press # to apply the new setting.
Medical Alarm Sound Rhythm
Default = 3 (Alternate Modulated)
Police Siren Cadence
Default = 5 (Steady)
Auxiliary Alarm Sound Rhythm
Default = 4 (Fast Modulated)
17084
Set the alarm type to the desired sound rhythm.
Sound Rhythm Format (_ represents 0.125 second sound,
___represents 0.5 second sound).
q
1— Temporal 3 ___
q
2— Modulated ___
q
3— Alternate Modulated ___ _ _ ___ (repeat)
q
4— Fast Modulated _ _ _ _ _ _ _ _ _ (repeat)
q
5— Steady ___________ (steady on)
q
6— Programmable (must program through downloader)
To Set Alarm Sound Rhythm:
1. Once in program mode enter the desired item number.
2. Enter the desired sound rhythm (1–6) and press #.
___
___
(silence) (repeat)
___
___ ___(repeat)
Commercial Burglary and Home Navigator System
17126
17111
17128
17046
17047
17048