Raising And Lowering Frequency References Using Contact Signals (Up/Down) - Omron SYSDRIVE 3G3RV Series User Manual

High-function general-purpose inverters
Table of Contents

Advertisement

nApplication Precautions
When d4-01 is set to 1, the output frequency on hold is stored even after the power supply is turned OFF. If
performing operations using this frequency after the Inverter has also been turned OFF, input the run com-
mand with the Acceleration/Deceleration Ramp Hold turned ON.
When d4-01 is set to 0 and a run command is input while the Acceleration/Deceleration Ramp Hold is
turned ON, the output frequency will be set to zero.
If you input an Acceleration/Deceleration Ramp Hold command by error when decelerating during posi-
tioning, deceleration may be canceled.
K K K K
Raising and Lowering Frequency References Using Contact Signals (UP/
DOWN)
The UP and DOWN commands raise and lower Inverter frequency references by turning ON and OFF a multi-
function contact input terminal S3 to S7.
To use this function, set one of the parameters H1-01 to H1-05 (multi-function input terminal S3 to S7 func-
tion selection) to 10 (UP command) and 11 (DOWN command). Be sure to allocate two terminals so that the
UP and DOWN commands can be used as a pair.
The output frequency depends on the acceleration and deceleration time. Be sure to set b1-02 (Run command
selection) to 1 (Control circuit terminal).
nRelated Parameters
Name
Param-
eter
Num-
LCD Display
ber
Frequency reference upper
limit
d2-01
Ref Upper Limit
Frequency reference lower
limit
d2-02
Ref Lower Limit
Master speed reference
lower limit
d2-03
Ref1 Lower Limit
nPrecautions
When setting and using UP and DOWN commands, observe the following precautions.
Setting Precautions
If multi-function input terminals S3 to S7 are set as follows, operation error OPE03 (Invalid multi-function
input selection) will occur:
Only either the UP command or DOWN command has been set.
UP/DOWN commands and Acceleration/Deceleration Ramp Hold have been allocated at the same time.
Description
Set the output frequency upper limit as a percent,
taking the maximum output frequency to be 100%.
Set the output frequency lower limit as a percent-
age of the maximum output frequency.
Set the master speed frequency reference lower
limit as a percent, taking the maximum output fre-
quency to be 100%.
Input Terminal Functions
Control Methods
Change
Setting
Factory
during
Range
Setting
Opera-
V/f
tion
0.0 to
100.0%
No
A
110.0
0.0 to
0.0%
No
A
110.0
0.0 to
0.0%
No
A
110.0
Open
V/f
Loop
with
Vec-
PG
tor
A
A
A
A
A
A
65
6-