nSetting Motor Protection Operation Time
Set the motor protection operation time in L1-02.
If, after operating the motor continuously at the rated current, a 150% overload is experienced, set the (hot
start) electronic thermal protection operation time. The factory setting is resistance to 150% for 60 seconds.
The following diagram shows an example of the characteristics of the electronic thermal protection operation
time (L1-02 = 1.0 min., operation at 60 Hz, general-purpose motor characteristics, when L1-01 is set to 1)
Operating time (min.)
nSetting Precautions
If multiple motors are connected to one Inverter, set parameter L1-01 to 0 (disabled). To protect the motor,
install a thermal relay in the motor power cable, and perform overload protection on each motor.
With applications where the power supply is often turned ON and OFF, there is a risk that the circuit can-
not be protected even if this parameter has been set to 1 (enabled), because the thermal value will be reset.
To detect overloads in good time, set the set value in parameter L1-02 to a low setting.
When using a general-purpose motor (standard motor), the cooling ability will be lowered by f
quency). Consequently, the frequency may cause motor overload protection (OL1) to occur, even below
the rated current. If operating using the rated current at a low frequency, use a special motor.
nSetting the Motor Overload Pre-Alarm
If the motor overload protection function is enabled (i.e., L1-01 is set to other than 0) and you set H2-01 to
H2-03 (multi-function output terminals M1-M2, P1-PC, M3-M4, M5-M6, and P2-PC function selection) to 1F
(motor overload OL1 pre-alarm), the motor overload pre-alarm will be enabled. If the electronic thermal value
reaches minimum 90% of the overload detection level, the output terminal that has been set will be turned ON.
Cold start
Hot start
Motor current (%)
E2-01 is set to 100%
Fig 6.39 Motor Protection Operation Time
Machine Protection
1/4
(fre-
49