Setting the Frequency Reference
5-5-4
Setting Frequency References through Key Sequences
Setting Frequency References 1 through 8 and the Inching Frequency
Command (n21 through n28 and n29)
Setting Frequency References 1 through 8 (n21 through n28)
n21
Setting
0.0 to max. frequency
range
n22
Setting
0.0 to max. frequency
range
n23
Setting
0.0 to max. frequency
range
n24
Setting
0.0 to max. frequency
range
n25
Setting
0.0 to max. frequency
range
n26
Setting
0.0 to max. frequency
range
n27
Setting
0.0 to max. frequency
range
n28
Setting
0.0 to max. frequency
range
The following description provides information on parameters related to
frequency reference settings through key sequences on the Digital Operator
A total of nine frequency references (frequency references 1 through 8) and
an inching frequency command can be set together in the Inverter.
Frequency Reference 1
Unit of
setting
Frequency Reference 2
Unit of
setting
Frequency Reference 3
Unit of
setting
Frequency Reference 4
Unit of
setting
Frequency Reference 5
Unit of
setting
Frequency Reference 6
Unit of
setting
Frequency Reference 7
Unit of
setting
Frequency Reference 8
Unit of
setting
Note
1. Values will be set in 0.1-Hz increments if the frequency is less than 100 Hz
and 1-Hz increments if the frequency is 100 Hz or over.
2. Frequency reference 1 is enabled with n03 for frequency reference
selection set to 1.
3. Frequency references 2 through 8 are enabled by setting multi-step speed
references 1, 2, and 3 in n36 through n39 for multi-function input. Refer to
the following table for the relationship between multi-step speed references
1 through 3 and frequency references 1 through 8.
Changes during
operation
0.01 Hz
Default setting
(see note 1)
Changes during
operation
0.01 Hz
Default setting
(see note 1)
Changes during
operation
0.01 Hz
Default setting
(see note 1)
Changes during
operation
0.01 Hz
Default setting
(see note 1)
Changes during
operation
0.01 Hz
Default setting
(see note 1)
Changes during
operation
0.01 Hz
Default setting
(see note 1)
Changes during
operation
0.01 Hz
Default setting
(see note 1)
Changes during
operation
0.01 Hz
Default setting
(see note 1)
Chapter 5-5
Yes
6.0
Yes
0.0
Yes
0.0
Yes
0.0
Yes
0.0
Yes
0.0
Yes
0.0
Yes
0.0
57