Using An Analog Operator - Omron SYSDRIVE 3G3RV Series User Manual

High-function general-purpose inverters
Table of Contents

Advertisement

K K K K

Using an Analog Operator

This example shows wiring for using an Analog Operator. The Analog Operator model number is 3G3IV-
PJVOP95o or 3G3IV-PJVOP96o.
This example shows wiring for the 3G3RV-A2075 (200-V class Inverters of 7.5 kW)
3-phase power
o,
3G3IV-PJVOP-95
o Analog Operator
C-96
-10
10
Short-circuit bar
(Standard)
MCCB
Frequency meter
R/L1
U/T1
Inverter
V/T2
S/L2
W/T3
T/L3
Forward run command
(forward run when closed)
Reverse
run
command
(reverse run when closed)
Multi-function contact inputs
Sequence common (0 V)
Shield terminal
Speed setting power (15 V, 20 mA)
Master speed (0 to 10 V, 20 kΩ)
Master speed (4 to 20 mA, 250 Ω)
Multi-function contact
output (Default: Running
signal)
Fault contact output
Multi-function
analog output
Multi-function
analog output
(Default: Output
frequency)
Fig 10.6
Motor
Ground to 100
max.
Open collector 1 (Default:
Zero speed signal)
Multi-function open-
Open collector 2 (Default:
collector output 48 V,
Speed agreement signal)
50 mA max.
Multi-function output
common