n Parameter Settings for Autotuning
The following parameters must be set before autotuning.
Param-
eter
Name
Num-
ber
Set the location where the autotuned
motor constants are to be stored.
Motor 1/2
T1-00
1: E1 to E2 (motor 1)
selection
2: E3 to E4 (motor 2)
Set the autotuning mode.
Autotuning
0: Rotational autotuning
T1-01
mode selec-
1: Stationary autotuning
tion
2: Stationary autotuning for line-to-
Set the output power of the motor in
Motor out-
T1-02
put power
kilowatts.
Set the rated voltage of the motor in
Motor rated
T1-03
voltage
volts.
Set the rated current of the motor in
Motor rated
T1-04
current
amps.
Set the base frequency of the motor
Motor base
T1-05
frequency
in hertz.
Number of
T1-06
Set the number of motor poles.
motor poles
Set the base speed of the motor in
Motor base
T1-07
speed
r/min.
* 1. Not normally displayed. Displayed only when a motor switch command is set for a multi-function digital input (one of H1-01 to H1-05 set to 16).
* 2. Only a setting of 2 (stationary autotuning for line-to-line resistance only) is possible for V/f control or V/f control with PG.
* 3. For a constant-output motor, set the value at the base speed.
* 4. For an inverter motor or vector motor, the voltage and frequency may be lower than for a general-purpose motor. Always confirm setting on the name-
plate or in test reports. Also, if you know the no-load values, set the no-load voltage in T1-03 and the no-load frequency in T1-05 to obtain better accu-
racy.
* 5. Stable vector control will be possible when the setting is between 50% and 100%.
* 6. The setting range depends on the Inverter capacity and the setting of C6-01 (CT/VT Selection).
Table 4.4 Parameter Settings before Autotuning
Display
*1
line resistance only
*3
*3 *4
*3
*3 *4
*3
Trial Operation Procedures
Data Displays during
Setting
Factory
Range
Setting
1 or 2
1
Yes
2 (V/f and
V/f with
Yes
PG)
0 to 2
(only
0 (open-
for 2)
loop vec-
*2
tor)
10% to 200%
Same as
of Inverter
Inverter
Yes
rated output
rated output
*5
200.0 V
0 to 255.0 V
(200 V
(200 V class)
class)
0 to 510.0 V
400.0 V
(400 V class)
(400 V
class)
Same as
general-
10% to 200%
purpose
of Inverter
motor with
Yes
rated cur-
same
*5
rent
capacity as
Inverter
0 to 400.0 Hz
60.0 Hz
*6
2 to 48 poles
4 poles
1750
0 to 24000
r/min
*6
Autotuning
V/f
Open
V/f
with
Loop
PG
Vector
Yes
Yes
Yes
(only
Yes
for 2)
Yes
Yes
-
-
Yes
Yes
Yes
-
-
Yes
-
-
Yes
-
-
Yes
13
4-