Omron SYSDRIVE 3G3RV Series User Manual page 305

High-function general-purpose inverters
Table of Contents

Advertisement

nError Codes
The following table shows RS-422A/485 communications error codes.
Error Code
Function code error
01H
A function code other than 03H, 08H, or 10H has been set by the PLC.
Invalid register number error
02H
• The register address you are attempting to access is not recorded anywhere.
• With broadcast sending, a start address other than 0000H, 0001H, or 0002H has been set.
Invalid quantity error
03H
• The Quantity (number of data item) in the command message must be in range between 1 to 16.
• In the write command message, the Numbers of attached data bytes must be twice of the Quantity.
Data setting error
• A simple upper limit or lower limit error has occurred in the control data or when writing parame-
21H
ters.
• When writing parameters, the parameter setting is invalid.
Write mode error
• Attempting to write parameters during operation.
• Attempting to write an ENTER command during operation.
22H
• Attempting to write parameters other than A1-00 to A1-05, E1-03, or 02-04 when warning alarm
CPF03 (defective EEPROM) has occurred.
• Attempting to write read-only data.
Writing during main circuit undervoltage (UV) error
23H
• Writing parameters from the PLC during UV (main circuit undervoltage) alarm.
• Writing ENTER commands from the PLC during UV (main circuit undervoltage) alarm.
Writing error during parameters processing
24H
Attempting to write parameters from the PLC while processing parameters in the Inverter.
nSlave Not Responding
In the following cases, the slave will ignore the write function. If the slave address specified in the command
message is 0, all slaves execute the write function, but do not return response messages to the master.
When a communications error (overrun, framing, parity, or CRC-16) is detected in the command message.
When the slave address in the command message and the slave address in the Inverter do not agree.
When the data that configures the message and the data time length exceeds 24 bits.
When the command message data length is invalid.
Application Precautions
Set a timer in the master to monitor response time from the slaves. Make the setting so that if no response is
sent to the master from the slave within the set time, the same command message is sent again from the mas-
ter.
Communications Functions
Contents
89
6-

Advertisement

Table of Contents

Troubleshooting

loading

This manual is also suitable for:

Sysdrive 3g3rv-a2004Sysdrive 3g3rv-a2004-eSysdrive 3g3rv-a2007Sysdrive 3g3rv-a2007-eSysdrive 3g3rv-a2015Sysdrive 3g3rv-a2015-e ... Show all

Table of Contents