nComparing Inverter Parameters and Digital Operator Parameter Set Values (VERIFY)
To compare Inverter parameters and Digital Operator parameter set values, make the settings using the follow-
ing method.
Step
No.
1
2
3
4
5
6
7
An error may occur during the comparison. If an error is displayed, press any key to cancel the error display
and return to the o3-01 display. Error displays and their meanings are shown below. (Refer to Chapter 7
Errors when Using Digital Operator Copy Function.)
Error Display
nApplication Precautions
When using the copy function, check that the following settings are the same between the Inverter and the
Digital Operator.
•
Inverter product and type
Software number
•
-140
6
Table 6.8 VERIFY Function Procedure
Digital Operator Display
DRIVE QUICK
ADV
VERIFY
AUTO
TUNING
DRIVE QUICK
ADV
VERIFY
AUTO
TUNING
DRIVE QUICK
ADV
VERIFY
AUTO
TUNING
DRIVE QUICK
ADV
VERIFY
AUTO
TUNING
DRIVE QUICK
ADV
VERIFY
AUTO
TUNING
DRIVE QUICK
ADV
VERIFY
AUTO
TUNING
Verify error (Settings in the Digital Operator and the Inverter do not match).
Press the MENU Key. and select advanced pro-
gramming mode.
Press the ENTER Key, and select the parame-
ters monitor display.
Display o3-01 (Copy Function Selection) using
the Increment Key and Decrement Key.
Press the ENTER Key, and select the function
setting display.
Change the set value to 3 using the Increment
Key.
Set the changed data using the ENTER Key.
The VERIFY function will start.
If the VERIFY function ends normally, End is
displayed on the Digital Operator. Parameter
o3-01 is automatically reset to 0, and then the
display returns to o3-01.
Meaning
•
Inverter capacity and voltage
Control method
•
Explanation