Func-
Display
tion
READ
IMPOSSIBLE
Read
READ DATA
ERROR
DATA ERROR
ID UNMATCH
INV. KVA
UNMATCH
CONTROL
Copy
UNMATCH
COPY ERROR
SUM CHECK
ERROR
-14
7
Table 7.5 Errors during Copy Function
Meaning
o3-01 was set to 1 to write a parameter
Digital Operator
when the Digital Operator was write-
write-protected
protected (o3-02 = 0).
The read data length does not agree.
Illegal read data
The write data is incorrect.
An attempted write of a parameter to
Illegal write status
EEPROM on the Digital Writer failed.
The Inverter product code or software
ID not matched
number is different.
The capacity of the Inverter being
Inverter capacity
copied and the capacity in the Digital
matched
Operator are different.
The control method of the Inverter
Control method
being copied and the control method
matched
in the Digital Operator are different.
The parameter written to the Inverter
was compared with the parameter in
Verify error
the Digital Operator and they were
different.
The checksum in the Inverter parame-
ter area was compared with the check-
Checksum error
sum in the Digital Operator parameter
area and they were different.
Probable causes
Corrective Actions
Set o3-02 to 1 to enable writing
parameters with the Digital Operator.
Repeat the read.
Check the Digital Operator cable.
Replace the Digital Operator.
A low Inverter voltage has been
detected.
Repeat the read.
Replace the Digital Operator.
Use the copy function for the same
product code and software number.
Use the copy function for the same
Inverter capacity.
Use the copy function for the same
control method.
Retry the copy.
Retry the copy.