Omron SYSDRIVE 3G3RV Series User Manual page 142

High-function general-purpose inverters
Table of Contents

Advertisement

Param-
eter
Number
Display
PID output
gain
b5-10
Output Gain
PID reverse
output
selection
b5-11
Output Rev
Sel
Selection of
PID feed-
back com-
mand loss
detection
b5-12
Fb los Det
Sel
PID feed-
back com-
mand loss
detection
b5-13
level
Fb los Det
Lvl
PID feed-
back com-
mand loss
detection
b5-14
time
Fb los Det
Time
PID sleep
function
operation
level
b5-15
PID Sleep
Level
PID sleep
operation
delay time
b5-16
PID Sleep
Time
-16
5
Name
Description
LCD
Sets output gain.
0: 0 limit when PID output
is negative.
1: Reverses when PID
output is negative.
0 limit when reverse prohibit
is selected using b1-04.
0: No detection of loss of
PID feedback.
1: Detection of loss of PID
feedback.
Operation continues
during detection, with the
malfunctioning contact
not operating.
2: Detection of loss of PID
feedback.
Coasts to stop during
detection, and fault
contact operates.
Sets the PID feedback loss
detection level as a percent
units, with the maximum
output frequency at 100%.
Sets the PID feedback loss
detection level in seconds.
Set the PID sleep function
start level as a frequency.
Always enabled for (-E)
models. On other models, it
is disabled when the PID
control is not selected
(b5-01=0).
Set the delay time until the
PID sleep function starts in
seconds.
Control Methods
Change
during
Setting
Factory
Range
Setting
Opera-
V/f
tion
0.0 to
1.0
No
25.0
0 or 1
0
No
0 to 2
0
No
0 to
0%
No
100
0.0 to
1.0 s
No
25.5
0.0 to
0.0 Hz
No
400.0
0.0 to
0.0 s
No
25.5
V/f
Register Page
Open
with
Loop
PG
A
A
A
1AEH
A
A
A
1AFH
A
A
A
1B0H
A
A
A
1B1H
A
A
A
1B2H
A
A
A
1B3H
A
A
A
1B4H
6-118
6-118
6-118
6-118
6-118
6-118
6-119