Param-
eter
Number
Display
Stall pre-
vention
selection
during decel
L3-04
StallP Decel
Sel
Stall pre-
vention
selection
during run-
ning
L3-05
StallP Run
Sel
Stall pre-
vention
level during
running
L3-06
StallP Run
Level
* The initial value when C6-01 is set to 1 is given. If C6-01 is set to 0, the initial value will be 150%.
-60
5
Name
Description
LCD
0: Disabled (Deceleration as
set. If deceleration time is
too short, a main circuit
overvoltage may result.)
1: Enabled (Deceleration is
stopped when the main
circuit voltage exceeds
the overvoltage level.
Deceleration restarts
when voltage is returned.)
2: Intelligent deceleration
mode (Deceleration rate
is automatically adjusted
so that in Inverter can
decelerate in the shortest
possible time. Set
deceleration time is
disregarded.)
3: Enabled (with Braking
Resistor Unit)
When a braking option
(Braking Resistor, Braking
Resistor Unit, Braking Unit)
is used, always set to 0 or 3.
0: Disabled (Runs as set.
With a heavy load, the
motor may stall.)
1: Deceleration time 1 (the
deceleration time for the
stall prevention function
is C1-02.)
2: Deceleration time 2 (the
deceleration time for the
stall prevention function
is C1-04.)
Effective when L3-05 is 1 or
2.
Set as a percentage of the
Inverter rated current.
Usually setting is not neces-
sary.
The factory setting reduces
the set values when the
motor stalls.
Control Methods
Change
during
Setting
Factory
Range
Setting
Opera-
V/f
tion
0 to 3
1
No
0 to 2
1
No
30 to
120%
No
200
*
V/f
Register Page
Open
with
Loop
PG
Q
Q
Q
492H
A
A
No
493H
A
A
No
494H
4-8
6-25
6-42
6-42