Communication
' '
'
'
sequence
Inverter I/O Send &

Recv
Sequence number. The sequence number is automatically set.
Communication Sequence
The label (name) of the sequence. Input an appropriate, easy-to-distinguish name.
Link Word
Set the area for sharing the data between the Programmable Controller and Communications Board.
In this example, the link word is specified by the operand of the PMCR instruction. Therefore no link word is
set here.
Control
Set the control method, such as flow control.
Select only "modem control" for communications with the 3G3RV.
Response
A method to write reception data to the I/O memory of the Programmable Controller.
Select "notify by scan" for communications with the 3G3RV.
Timer Tr, Timer Tfr, and Timer Tfs
Set the periods to monitor the transmission and reception steps with timers Tr, Tfr, and Tfs. The following tim-
ing chart shows the meaning of each monitor.
Be sure to set the periods according to the application.
The step will be retried if the step is not completed within the monitor periods. An error will occur if the step
is not completed within the monitor time again.
Set a period of approximately 0.5 s each for communications with the 3G3RV.
Ts
Send & Recv Send
Recv
Ts:
Send wait time set per step. Nothing is sent during this period.
Tfs:
Monitors the completion of the data sent. If the data transmission is not finished within this period,
the data will be re-transmitted.
Tr:
Monitors the response to be received. If the response is not returned within this period, the response will
be re-transmitted.
Tfr:
Monitors the reception completion of the response. If the response transmission is not finished within this
period, the response will be re-transmitted.
Note If the Tr period is too long, the time to detect a communications error will be longer, during which the Inverter
cannot be controlled. Therefore, be sure to set an appropriate period.
Link word
Control
'''
Set (Setting required)
Monitored for
Monitored for
Tr period
Tfs period
Fig 6.67
Communications Functions
Timer
Timer
Response
Tr
Tfr
Scan
0.5
0.5
Monitored for
Tfr period
Timer
Tfs
0.5
103
6-