nInputting Frequency Reference Using Current
When b1-01 is set to 1, you can input the frequency reference from control circuit terminal A2. Input the cur-
rent (4 to 20 mA) in control circuit terminal A2.
When H3-09 (Multi-Function Analog Input Terminal A2 Signal Level Selection) is set to 0 (factory setting)
the input on A2 is added to A1.
Setting Precautions
When inputting a current signal to terminal A2, turn ON pin 2 on DIP switch S1 (factory setting: ON).
If using terminal A2 to input the master speed reference and terminal A1 to input the auxiliary frequency
reference, set H3-13 (Terminal A1/A2 Switching) to 1.
nSetting Frequency Reference Using Pulse Train Signals
When b1-01 is set to 4, the pulse train input to control circuit terminal RP is used as the frequency reference.
Set H6-01 (PulseTrain Input Function Selection) to 0 (frequency reference), and then set the 100% reference
pulse frequency to H6-02 (Pulse Train Input Scaling).
Pulse Input Specifications
Low level voltage
High level voltage
Heavy duty
Pulse frequency
Fig 6.9 Frequency Reference Using Pulse Train Input
Inverter
+V (Power supply: 15 V, 20 mA)
A1 (Auxiliary speed frequency
reference)
1 to 20 mA input
A2 (Master speed frequency
reference)
AC (Analog common)
DIP switch S1
Fig 6.8 Frequency Reference Using Current
0.0 to 0.8 V
3.5 to 13.2 V
32 kHz max.
30 to 70%
0 to 32 kHz
Pulse input
Inverter
3.5 to 13.2 V
RP(Pulse train input termi-
nal)
AC (Analog common)
Frequency Reference
6-
9