nWiring the 3G3FV-PPGD2
Wiring examples are provided in the following illustrations for the 3G3FV-PPGD2.
Three-phase 200
VAC (400 VAC)
Shielded twisted-pair wires must be used for signal lines.
Do not use the pulse generator's power supply for anything other than the pulse generator (encoder).
Using it for another purpose can cause malfunctions due to noise.
The length of the pulse generator's wiring must not be more than 50 meters.
nWiring the 3G3FV-PPGX2
Wiring examples are provided in the following illustrations for the 3G3FV-PPGX2.
Three-phase
200 VAC (400
VAC)
Shielded twisted-pair wires must be used for signal lines.
Do not use the pulse generator's power supply for anything other than the pulse generator (encoder).
Using it for another purpose can cause malfunctions due to noise.
The length of the pulse generator's wiring must not be more than 50 meters.
The direction of rotation of the PG can be set in parameter F1-05 (PG Rotation). The factory preset if for
motor forward rotation, A-phase advancement.
Inverter
3G3FV-PPGD2
Fig 2.40 3G3FV-PPGD2 Wiring
Inverter
R/L1
U/T1
S/L2
V/T2
T/L3
W/T3
3G3FV-PPGX2
Fig 2.41 3G3FV-PPGX2 Wiring
Installing and Wiring Option Cards
Power supply +12 V
Power supply 0 V
Power supply +5 V
Pulse input + (A/B phase)
Pulse input - (A/B phase)
Pulse monitor output
E6B2-CWZ1X
Power supply +12 V
Power supply 0 V
Power supply +5 V
A-phase pulse input (+)
A-phase pulse input (-)
B-phase pulse input (+)
B-phase pulse input (-)
A-phase pulse monitor output
B-phase pulse monitor output
Z-phase pulse monitor output
E6B2-CWZ1X