Omron SYSDRIVE 3G3RV Series User Manual page 116

High-function general-purpose inverters
Table of Contents

Advertisement

nSetting the Control Method
Any of the following three control methods can be set.
V/f control without PG (normal speed control)
V/f control with PG (simple speed feedback control)
Open-loop vector control (high-performance control without PG)
V/f Control without PG (A1-02 = 0)
Set either one of the fixed patterns (0 to E) in E1-03 (V/f Pattern Selection) or set F in E1-03 to specify a
user-set pattern as required for the motor and load characteristics in E1-04 to E1-13 in advanced program-
ming mode.
Simple operation of a general-purpose
motor at 50 Hz:
Simple operation of a general-purpose
motor at 60 Hz:
Perform stationary autotuning for the line-to-line resistance only if the motor cable is 50 m or longer for
the actual installation or the load is heavy enough to produce stalling. Refer to the following section on
Autotuning for details on stationary autotuning.
V/f Control with PG (A1-02=1)
Set either one of the fixed patterns (0 to E) in E1-03 (V/f Pattern Selection) or set F in E1-03 to specify a
user-set pattern as required for the motor and load characteristics in E1-04 to E1-13 in advanced program-
ming mode.
Simple operation of a general-purpose
motor at 50 Hz:
Simple operation of a general-purpose
motor at 60 Hz:
Set the number of motor poles in E2-04 (Number of Motor Poles)
Set the number of rotations per pulse in F1-01 (PG Constant). If there is a reduction gear between the
motor and PG, set the reduction ratio in F1-12 and F1-13 in advanced programming mode.
Perform stationary autotuning for the line-to-line resistance only if the motor cable is 50 m or longer for
the actual installation or the load is heavy enough to produce stalling. Refer to the following section on
Autotuning for details on stationary autotuning.
Open-loop Vector Control (A1-02 = 2)
Perform autotuning. If the motor can be operated without a load, perform rotational autotuning. If the motor
cannot be operated, perform stationary autotuning. Refer to the following section on Autotuning for details on
autotuning.
-10
4
E1-03 = 0
E1-03 = F (default) or 1
If E1-03 = F, the default setting in the user setting from
E1-04 to E1-13 are for 60 Hz (50 Hz for -E models)
E1-03 = 0
E1-03 = F (default) or 1
If E1-03 = F, the default setting in the user setting from
E1-04 to E1-13 are for 60 Hz (50 Hz for -E models)

Advertisement

Table of Contents

Troubleshooting

loading

This manual is also suitable for:

Sysdrive 3g3rv-a2004Sysdrive 3g3rv-a2004-eSysdrive 3g3rv-a2007Sysdrive 3g3rv-a2007-eSysdrive 3g3rv-a2015Sysdrive 3g3rv-a2015-e ... Show all

Table of Contents