Cabinet Requirements For Ex2200 Switches - Juniper EX2200 Series Hardware Manual

Juniper networks switch user manual
Hide thumbs Also See for EX2200 Series:
Table of Contents

Advertisement

Complete Hardware Guide for EX2200 Ethernet Switches
Table 20: Rack Requirements and Specifications for the Switch (continued)
Rack Requirement
Rack size and strength
Rack connection to
building structure
Related
Documentation

Cabinet Requirements for EX2200 Switches

58
Guidelines
Ensure that the rack complies with the standard defined for 19-in. rack as defined in Cabinets,
Racks, Panels, and Associated Equipment (document number EIA-310–D) published by the
Electronics Industry Association (
Ensure that the rack rails are spaced widely enough to accommodate the switch chassis' external
dimensions . The outer edges of the front-mounting brackets extend the width of the chassis to
19 in. (48.2 cm).
The rack must be strong enough to support the weight of the switch.
Ensure that the spacing of rails and adjacent racks allows for the proper clearance around the
switch and rack.
Secure the rack to the building structure.
If earthquakes are a possibility in your geographical area, secure the rack to the floor.
Secure the rack to the ceiling brackets as well as wall or floor brackets for maximum stability.
One pair of mounting brackets for mounting the switch on two posts of a rack is supplied
with each switch. For mounting the switch on four posts of a rack or cabinet, you can
order a four-post rack-mount kit separately.
NOTE:
Mounting brackets are not supplied with EX2200-C switch; they are
separately orderable.
Chassis Physical Specifications for EX2200 Switches on page 9
Clearance Requirements for Airflow and Hardware Maintenance for EX2200 Switches
on page 60
Rack-Mounting and Cabinet-Mounting Warnings on page 167
Mounting an EX2200 Switch on Two Posts of a Rack or Cabinet on page 81
Mounting an EX2200 Switch on Four Posts of a Rack or Cabinet on page 84
Mounting an EX2200 Switch in a Recessed Position in a Rack or Cabinet on page 88
You can mount the switch in a cabinet that contains a 19-in. rack.
Cabinet requirements consist of:
Cabinet size
Clearance requirements
Cabinet airflow requirements
Table 21 on page 59
provides the cabinet requirements and specifications for the switch.
http://www.eia.org
).