Mounting And Clearance Requirements; Rack Requirements For Ex2200 Switches; Table 20: Rack Requirements And Specifications For The Switch - Juniper EX2200 Series Hardware Manual

Juniper networks switch user manual
Hide thumbs Also See for EX2200 Series:
Table of Contents

Advertisement

CHAPTER 5

Mounting and Clearance Requirements

Rack Requirements for EX2200 Switches

Table 20: Rack Requirements and Specifications for the Switch

Rack Requirement
Rack type
Mounting bracket hole
spacing
Copyright © 2011, Juniper Networks, Inc.
Rack Requirements for EX2200 Switches on page 57
Cabinet Requirements for EX2200 Switches on page 58
Requirements for Mounting an EX2200 Switch on a Desktop or Wall on page 60
Clearance Requirements for Airflow and Hardware Maintenance for EX2200
Switches on page 60
You can mount the EX2200 switches on two-post racks or four-post racks.
Rack requirements consist of:
Rack type
Mounting bracket hole spacing
Rack size and strength
Rack connection to the building structure
Table 20 on page 57
provides the rack requirements and specifications for the switch.
Guidelines
Use a two-post rack or a four-post rack. You can mount the switch on any two-post or four-post
rack that provides bracket holes or hole patterns spaced at 1 U (1.75 in./4.45 cm) increments and
that meets the size and strength requirements to support the weight.
A U is the standard rack unit defined in Cabinets, Racks, Panels, and Associated Equipment (document
number EIA-310–D) published by the Electronics Industry Association (
The rack must meet the strength requirements to support the weight of the chassis.
The holes in the mounting brackets are spaced at 1 U (1.75 in. or 4.45 cm), so that the switch can
be mounted in any rack that provides holes spaced at that distance.
http://www.eia.org
).
57