Grounding Cable Specifications; Cabinet Requirements For Acx2000 And Acx2100 Routers - Juniper ACX2000 Hardware Manual

Hide thumbs Also See for ACX2000:
Table of Contents

Advertisement

Figure 17: Grounding Cable Lug
1.69
End view
0.2
0.38
dia.
0.06
0.625
CAUTION:
lug to the grounding and power cables that you supply. A cable with an incorrectly
attached lug can damage the router.
CAUTION:
lb-in. (0.49 Nm). The grounding screws may be damaged if excessive torque is applied.
Use only a torque-controlled driver to tighten screws. Use an appropriately sized driver,
with a maximum torque capacity of 5 lb-in. or less. Ensure that the driver is undamaged
and properly calibrated and that you have been trained in its use. You may wish to use
a driver that is designed to prevent overtorque when the preset torque level is achieved.

Grounding Cable Specifications

You must provide one grounding cable that meets the following specifications: 6-AWG (4.11 mm
90°C wire, or as required by the local code.
SEE ALSO
Connecting the ACX2000 or ACX2100 Router to Earth Ground | 100
Prevention of Electrostatic Discharge Damage | 168

Cabinet Requirements for ACX2000 and ACX2100 Routers

You can mount the router in a cabinet that contains a 19-in. (48.3 cm) rack.
Cabinet requirements consist of:
Cabinet size
6 AWG conductor
All measurements in inches
Before router installation begins, a licensed electrician must attach a cable
The maximum torque rating of the grounding screws on the router is 4.34
76
2
), minimum