Table of Contents

Advertisement

NOTE: Install the router only in restricted areas, such as dedicated equipment rooms and
equipment closets, in accordance with Articles 110-16, 110-17, and 110-18 of the National
Electrical Code, ANSI/NFPA 70.

Cabinet Requirements for ACX4000 Routers

You can mount the router in a cabinet that contains a 19-in. (48.3 cm) rack.
Cabinet requirements consist of:
• Cabinet size
• Clearance requirements
• Cabinet airflow requirements
Table 24 on page 78
provides the cabinet requirements and specifications for the router.
Table 24: Cabinet Requirements and Specifications for the ACX4000 Router
Cabinet Requirement
Cabinet size
Guidelines
You can mount the router in a cabinet that
contains a 19-in. (48.3 cm) rack as defined in
Cabinets, Racks, Panels, and Associated Equipment
(document number EIA-310–D) published by the
Electronics Industry Association
www.eia.org).
NOTE: The rack must meet the strength
requirements to support the weight of the router.
The minimum cabinet size must be able to
accommodate the maximum external dimensions
of the router.
(http:/ /
78