Ccn Communication; Accessories - Carrier 50PD05 Operating And Service Instructions

Single package displacement ventilation or single zone variable airflow rooftop units electric cooling/gas heating with puron (r-410a) refrigerant and comfortlink 1.x controls
Hide thumbs Also See for 50PD05:
Table of Contents

Advertisement

Table
3 1
Application
Specific
Configurations
DISPLACEMENT
SINGLE
ZONE
ITEM
EXPANSION
DEFAULT
UNITS
VENTILATION
VAV
SASP
Cool Supply
Air Setpoint
65
dF
65
55
FS.MX
Supply
Fan Maximum
Speed
100
%
100
100
FS.MN
Supply
Fan Maximum
Speed
20
%
20
70
FS.VM
Vent Mode Fan Speed
50
^ F
50
50
M IN.C
M in Corn pressor Capacity
70
%
15
70
FS.CD
Fan Speed Control
Demand
3
^F
3
3
SA.MU
SASP Maximum
Reset Up
10
^F
3
5
SA.MD
SASP Maximum
Reset Down
-10
^F
-3
-5
MRMX
Econ Min at Max Fanspeed
30
%
30
30
PE1 .C
Power Exhaust
Stage
1 CFM
600
cfm
600
600
IDF.C
Indoor Fan Max Speed
CFM
1600 (05)
cfm
1600 (05)
1600 (05)
2000 (06)
2000 (06)
2000 (06)
System Pilot - Communication
Space Sensor
Install the System
Pilot and connect
the CCN communication
bus
from it to the units CCN connection
on the low voltage
terminal
board.
Configure
the unit's CCN communication
element
number,
bus number,
and baud
rate.
Refer to the System
Pilot's
installation
instructions
for configuring
it to be used as a space temperature
and
attaching
it to a unit.
gen III TEMP Monitor
- Linkage Communication
Thermostat (33CSTMT-01)
Install
the linkage
thermostat.
Connect
the CCN
communication
bus from
the Stat to the CCN
terminals
on the field connection
terminal
board
located
at the unit control
box. Configure
the unit's
CCN communication
element
number,
bus number,
and baud rate.
Refer
to
the
Linkage
Thermostat's
installation
instructions
for
configuring
the Stat and additional
information
about it.
Space Humidistat Control
The humidistat
input
is provided
on the field connection
terminal
board.
The
Space
Humidity
Switch
configuration,
Configuration--,UNIT--,RH.SW,
identifies
the normally
open
or
normally
closed status of this input
at LOW
humidity.
Humidistat
1 terminal
is the 24 VAC source
for dry contact
and the Humidistat
2 terminal
is the signal input.
Relative Humidity Sensor Control
For units with the economizer
option
(with the ECB-economizer
control
board),
the humidity
sensor
input is provided
on the field
connection
terminal
board.
The sensor can be used in addition
to
or instead
of a humidistat.
The
RH
Sensor
on
OAQ
Input
configuration,
Configuration-+UNIT-+RH.S=YES,
identifies
that
the sensor is being
used instead
of an OAQ sensor.
Terminal
1 is
the 24vdc loop power
and Terminal
4 is the 4-20
mA signal input.
Refer to the Field Installed
Accessories
for more information.
CCN Communication
Configure
Configuration--,CCN--,CCN,4
to
desired
element
number
(Default
is 1). Configure
Configuration-->CCN-->
CCN.B
to
desired
bus
number
(Default
is
0).
Configure
Configuration--+CCN--+BAUD
to desired
code number
for baud
rate (Default
is 3 = 9600 baud).
Accessories
Below
are
quick
configuration
settings
for
field
installed
accessories.
If these accessories
were installed
by the factory,
they
will already
be configured.
See the Field-Installed
Accessories
section,
third party control,
control
connection
tables, and CCN or
Display
parameter
tables for any accessories
not mentioned
below
and any additional
information
on accessories.
Economizer
If an Economizer
accessory
was field installed,
the unit must
be
configured
for it by setting
Configuration-->ECON-->EC.EN
to
YES. The default
settings
for the other economizer
configurations
should
be
satisfactory.
If they
need
to be
changed,
additional
information
about these configuration
settings
can be found
in the
Economizer
section.
Power Exhaust
If a Power Exhaust
accessory
was field installed,
the unit must be
configured
for it by setting
Configuration-->ECON-->PE,EN
to
ENBL.
The
default
settings
for
the
other
power
exhaust
configurations
should
be satisfactory.
If they need to be changed,
additional
information
about these configurations
can be found
in
the Power Exhaust
section.
Electric Heat
If an Electric
Heat
accessory
was field installed,
the unit must be
configured
for it by setting Configuration--,HEAT--,HT.TY
to a
value
of 2. The number
of electric
heat stages must be configured
by
setting
Configuration--,HEAT--,NJtTR
per
the
installed
heater.
Fire Shutdown
If a Fire
Shutdown
or
Smoke
Detector
accessory
was
field
installed,
the
unit
must
be
configured
for
it
by
setting
Configuration--,UNIT--,FS.SW
to normally
open (1) or normally
closed
(2) when
there is not a fire alarm. Normally
open (1) is the
preferred
configuration.
IMPORTANT:
On standard
units, the fire shutdown
input
is the
terminals
Fire Shutdown
1 and 2.
Outdoor Enthalpv
If an Outdoor
Enthalpy
accessory
was field installed,
the unit must
be configured
for it by setting Configuration--,ECON--,EN.SW,
identifies
the normally
open or normally
closed status of this input
when the outdoor
enthalpy
is low.
IAQ Switch
If an IAQ Switch
accessory
was field installed,
the unit must be
configured
for
it
by
setting
Configuration--,AIR.Q--,II.CF,
identifies
the normally
open or normally
closed status of this input
when the indoor
air quality
value is low (good) and also selects the
unit response
to this input.
IMPORTANT:
An IAQ
switch
cannot
be used if an enthalpy
switch
is already
on this input.
IAQ
Sensor
If an CO 2 Sensor
accessory
was field installed,
the unit must be
configured
for
it
by
setting
Configuration-+AIR.Q-+IA.CF
selects
the unit response
to this input.
Default
conversion
to 0 to
2000 ppm.
OAQ
Sensor
If an Outdoor
Air Quality
Sensor
accessory
was field installed,
the
unit must be configured
for it by setting
Configuration-+AIR.Q
--,OA.CF
selects
the
unit
response
to
this
input.
Default
conversion
to 0 to 2000 ppm.

Advertisement

Table of Contents
loading

This manual is also suitable for:

48pd0550pd0648pd06

Table of Contents