Carrier 50PD05 Operating And Service Instructions page 21

Single package displacement ventilation or single zone variable airflow rooftop units electric cooling/gas heating with puron (r-410a) refrigerant and comfortlink 1.x controls
Hide thumbs Also See for 50PD05:
Table of Contents

Advertisement

beextended
by 15seconds. The n_axinmm
delay i s
3 minutes.
Once modified
by the IGC, the fan off delay will not change back
to
the
configured
Fan-off
Delay,
Gas
Heat
(Configuration--,HEAT--,FOD.G)
unless
power
is reset
to the
control.
A light emitting
diode
(LED)
is provided
on the IGC to indicate
status.
During
normal
operation
the LED is continuously
on.
See
the Troubleshooting
section
if the LED is off or flashing.
The IGC
is located behind
the gas section access panel door.
See Figure
8 or
9 for location.
The
48/50PD
unit
control
will
switch
automatically
between
cooling
and heating
to maintain
space
temperature.
To nfininfize
unnecessary
changes
there is a 10 nfinute
Mode
Select Timeguard
(Operating
Modes'--,HEAT--,MS.TG)
after
the
last
stage
of
cooling
turns off and before the heating
is allowed.
The unit tries to maintain
the space
temperature
at the Occupied
Heat Setpoint
(Setpoint--,OHSP)
or the Unoccupied
Heat Setpoint
(Setpoint--,UHSP).
See the Occupancy
Deternfination
section
for
factors
that
affect
the
Currently
Occupied
(Run
Status--,VIEW--,OCC)
parameter.
Heating
Demand
(Operating
Modes'--,HEAT--,SPT--,DMDJt)
is equal
to
the
occupied
or
unoccupied
set point
nfinus
the
Space
Temperature
(Operating
Modes'--,HEAT--,SPT--,SPT)
[DMDJt
= Setpoint
- SPT].
Two methods
are used to add and remove
stages
of heating
for
48PD units.
The first method
causes
the unit to operate
around
its
steady state number
of stages.
For example,
if the correct
number
of stages is between
0 and 1, this method
will cause the first stage
to cycle.
If the correct
number
of stages is between
1 and 2, this
method
will cause
the second
stage to cycle.
The second
method
causes the unit to find the steady-state
number
of stages.
Details of
these methods
are provided
below.
The control
uses two methods
to add a stage of heating.
The first
method
will add a stage
of heating
when
the Heating
Demand
(Operating
Modes---,HEAT---,SPT---,DMDdt)
plus the change
in
Spacetemp
Trend
(Operating
Modes---,HEAT---,SPT---,TRND)
times
the
Heat
Thermal
Lag
Factor
(Operating
Modes---,HEAT---,SPT---,H.LAG)
is greater
than
the
SPT
Heat
Demand
(+) Level
(Operating
Modes---,HEAT---,SPT---,HTaUD)
[DMD.H
+ change
TRND
* H.LAG
> HT.PD].
The second
method
will add a stage of heating
when Heat Demand
(Operating
Modes---,HEAT---,SPT---,DMDdt)
is greater
that the
SPT
Heat
Demand
(+)
Level
(Operating
Modes---,HEAT---,SPT---,HT.PD)
plus 0.5 degrees
F [DMD.H
>
HT.PD
+ 0.5] and the heat demand
is changing
at a rate greater
than 0.3 degrees
F per nfinute.
The control
uses two methods
to remove
a stage of heating.
The
first method
will
remove
a stage
of heating
when
the Heating
Demand
(Operating
Modes---,HEAT---,SPT---,DMDdt)
plus the
change
in
Spacetemp
Trend
(Operating
Modes---,HEAT---,SPT---,TRND)
times
the
Heat
Thermal
Lag
Factor
(Operating
Modes---,HEAT---,SPT---,H.LAG)
is less than
the
SPT
Heat
Demand
(-)
Level
(Operating
Modes---,HEAT---,SPT---,HT_D)
[DMDdt
+ change
TRND
*
H_LAG
< HT_D].
The second
method
will remove
a stage
of heating
when
Heat
Demand
(Operating
Modes---,HEAT---,SPT---,DMDdt)
is less that
the
SPT
Heat
Demand
(-)
Level
(Operating
Modes---,HEAT---,SPT---,HT.ND)
nfinus
0.5 degrees
F [DMDdt
<
HT.PD
- 0.5] and the heat demand
is changing
at a rate greater
than 0.3 degrees
F per nfinute.
Configurable
delays
also apply when adding
stages per Heat Stage
Increase
Time
(Configuration---,HEAT---,HdNC)
or
removing
stages
per
Heat
Stage
Decrease
Time
(Configuration---,HEAT---,H_DEC).
Heat
Mininmm
On
Time
(Configuration---,HEAT---,MRTdt)
and Heat Minimum
Off Time
(Configuration---,HEAT---,MOTdt)
also apply.
Supply-Air
Temperature
Sensor
(SAT)
The
SAT
Heat
Mode
Sensing
(Configuration--,HEAT--,SAT--,SATJt)
affects
the
Supply
Air
Temperature
(Temperatures'--,AIR.T--,SAT)
value displayed.
This
configuration
is accessible
via the Scrolling
Marquee
on the SAT
Heat Mode
Sensing
(Configuration--,HEAT--,SAT--,SATJt).
When
the
SAT
Heat
Mode
Sensing
(Configuration--,HEAT--,SAT--,SATJt)
=DSBL,
the Supply
Air
Temperature
(Temperatures---,AIR.T---,SAT)
value
on
the
Scrolling
Marquee
and the CCN tables will be forced to zero when
heat outputs
come ON and for 5 nfinutes
after.
The default
Supply
Air Temperature
(Temperatures---,AIR.T---,SAT)
location
is at the
fan inlet, upstream
of the heat section.
When
the
SAT
Heat
Mode
Sensing
(Configuration---,HEAT---,SAT---,SATdt)
=ENBL,
the Supply
Air
Temperature
(Temperatures---,AIR.T---,SAT)
sensor
reading
is
displayed
at
the Scrolling
Marquee
and the CCN
tables
during
heating
mode.
This setting should only be used if the original
SAT
sensor
wires are removed
from
the Main Base Board
(MBB)
and
replaced
by an accessory
SAT sensor
located
in the supply
duct
downstream
of the heat section.
There
are then
two supply
air
temperature
limits that become
active,
the Maximum
SAT Lower
Level
(Configuration---,HEAT---,SAT---,SAM_L)
the
Maximum
SAT
Upper
Level
(Configuration---,HEAT---,SAT---,SAM.U).
Any
time
the supply
air temperature
rises above
the Maximum
SAT Lower
Level
(Configuration---,HEAT---,SAT---,SAM_L)
the
heat
staging
will
be
linfited
to
what
is currently
on
and
no
additional
stages can be added until the supply
air temperature
falls
below
the
Maximum
SAT
Lower
Level
(Configuration---,HEAT---,SAT---,SAM.L).
If
the
supply
air
temperature
rises
above
the
Maximum
SAT
Upper
Level
(Configuration---,HEAT---,SAT---,SAM.U),
then
heating
will be
reduced
by removing
a heat stage.
That stage can not be added
again
until
the
Supply
Air
Temperature
(Temperatures---,AIR.T---,SAT)
falls
below
the
Maximum
SAT
Lower
Level
(Configuration---,HEAT---,SAT---,SAM_L).
If the
supply
air temperature
stays
above
the
Maximum
SAT
Upper
Level
(Configuration--,HEAT--,SAT--,SAM.U),
then
another
stage
will
be
removed
after
the
Heat
Stage
Decrease
Time
(Configuration---,HEAT---,H_DEC).
In heating
mode
the PD control
will maintain
the Occupied
Heat
Set Point
(Setpoint--_OHSP)
or the Unoccupied
Heat
Set Point
(Setpoint---,UHSP)
by turning
on or off the Stage
I and Stage 2
Gas
Heat
at
the
Supply
Fan
Minimum
Speed
(Configuration---,
UNIT---,FS_N).
When
the space
temperature
sensor detects
the space
temperature
below
the
Occupied
Heat
Set
Point
(Setpoint---,OHSP)
or
Unoccupied
Heat Set Point (Setpoint---,UHSP)
and power
is sent
to the
Integrated
Gas Unit
Controller
(IGC)
board.
The heat
staging
is deternfined
as described
above
and the Integrated
Gas
Controller
(IGC) initiates
the gas heat module
start-up.
Gas Heat Start-Up
An LED (light-enfitting
diode) on the IGC board will be on during
normal
operation.
A check is made to ensure that the rollout switch
and linfit switch are closed and the induced-draft
motor is running.
The
induced-draft
motor
is then energized,
and
when
speed
is
proven
with
the Hall
Effect
sensor
on the
motor,
the ignition
activation
period begins.
The burners
will ignite within
5 seconds.
If the burners
do not light,
there
is a 22-second
delay
before
another
5-second
attempt.
If the burners
still
do not light,
this
sequence
is repeated
for 15 nfinutes.
After the
15 nfinutes
have
elapsed,
if the burners
still have
not lit, heating
is locked
out.
When
ignition
occurs
the IGC board will continue
to monitor
the
condition
of the rollout
and linfit switches,
the Hall Effect sensor,
as well as the flame sensor. If for some reason
the over temperature
linfit opens
prior to the start of the indoor
fan blower,
on the next
attempt,
the 45-second
delay
will be shortened
to 5 seconds
less
than the time from initiation
of heat to when
the linfit tripped.
Gas
21