Carrier 50PD05 Operating And Service Instructions page 29

Single package displacement ventilation or single zone variable airflow rooftop units electric cooling/gas heating with puron (r-410a) refrigerant and comfortlink 1.x controls
Hide thumbs Also See for 50PD05:
Table of Contents

Advertisement

Table
8 -- ComfortLink
T_,Alarm
Codes
ALARM
OR
ALERT
NUMBER
T051
T064
T066
T073
T074
T075
T076
T077
T092
T102
Tl10
T126
T133
T143
T153
A154
T155
A156
A157
DESCRIPTION
Digital Compressor
Control Board Alarm
Compressor
A1 Safety Trip
Service Test - Compressor
A1 Safety Trip
Compressor
A1 Current Detected After
Turnoff
Service Test - Compressor
A1 Current
Detected After Turnoff
Circuit A Saturated Condensing
Temp
Thermistor
Failure
Circuit A Saturated Suction Temperature
Thermistor
Failure
Outdoor Air Temperature
Thermistor
Failure
Space Temperature
Thermistor
Failure
Supply Air Temperature
Thermistor
Failure
Return Air Thermistor
Failure
Space Relative Humidity Sensor Failure
Circuit A Suction Pressure Transducer
Failure
Compressor
A1 Current Sensor Failure
Circuit A Loss of Charge
Service Test - Circuit A Loss of Charge
Circuit A High Discharge
Pressure
Service Test - Circuit A High Discharge
Pressure
Circuit A Low Refrigerant
Pressure
Service Test - Circuit A Low Refrigerant
Pressure
Circuit
A Failure
To Pressurize
Service
Test
-
Circuit
A Failure
To
Pressurize
ACTION TAKEN BY
CONTROL
Real Timeclock
Hardware
Failure
Serial
EEPROM
Hardware
Failure
Serial
EEPRQM
Storage
Failure
Error
Critical
Serial
EEPRQM
Storage
Fail Error
A/D
Hardware
Failure
Circuit
A Down
Due to Failure
Service
Test
-
Circuit
A Down
Due to
Failure
No action
Add Strike for Circuit A
Add Strike for Circuit A
Turn off all
compressors
Turn off all
compressors
Use OAT to control
Outdoor fans
No Cooling
No cooling with
economizer
No heating or cooling
No cooling mode
No differential
DB
crossover
If RH.S = Yes, then no
indoor humidity
control
Shutdown
Circuit A
If CS.A1 = Enable,
then no T051 current
alarm
Shutdown
Circuit A
Shutdown
Circuit A
Shutdown
Circuit A
Shutdown
Circuit A
Add Strike for Circuit A
Add Strike for Circuit A
Add Strike
for Circuit
A
Add Strike
for Circuit
A
No time
and
date
schedule
operation
Unit Shutdown
Unit operation
errors
Unit Shutdown
Unit Shutdown
Shutdown
Circuit
A
RESET
METHOD
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Manual
Automatic
Manual
Manual
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Manual
A163
Shutdown
Circuit A
Manual
PROBABLE
CAUSE
See the DSC's LEDs for troubleshooting
Current Sensing turned on (CS.A1 = Enable) and
should
be off
Current Sensing turned on (CS.A1 = Enable) and
should
be off
Current Sensing turned on (CS.A1 = Enable) and
should
be off
Current Sensing turned on (CS.A1 = Enable) and
should
be off
Faulty, shorted, or open thermistor
caused by wiring
error or loose connection.
Suction transducers
internally forced inactive
Faulty, shorted, or open thermistor
caused by wiring
error or loose connection.
Faulty, shorted, or open thermistor
caused by wiring
error or loose connection.
Faulty, shorted, or open thermistor
caused by wiring
error or loose connection.
Faulty, shorted, or open thermistor
caused by wiring
error or loose connection.
Faulty, shorted, or open sensor caused by wiring
error or loose connection.
Faulty transducer,
faulty 5-V
power supply, or loose
connection
Current Sensing turned on (CS.A1 = Enable) and
should
be off
Low refrigerant
or faulty suction pressure transducer
Low refrigerant
or faulty suction pressure transducer
An overcharged
system, high outdoor ambient
temperature
coupled with dirty outdoor
coil, plugged
filter drier, or a faulty high-pressure
switch.
An overcharged
system, high outdoor ambient
temperature
coupled with dirty outdoor
coil, plugged
filter drier, or a faulty high-pressure
switch.
Low refrigerant
charge, dirty filters, evaporator
fan
turning
backwards,
loose or broken fan belt, plugged
filter drier, faulty transducer,
excessively
cold return
air, or stuck open economizer
when the ambient
temperature
is low.
Low refrigerant
charge, dirty filters, evaporator
fan
turning
backwards,
loose or broken fan belt, plugged
filter drier, faulty transducer,
excessively
cold return
air, or stuck open economizer
when the ambient
temperature
is low.
Wiring causing
reverse rotation or faulty compressor
Wiring causing
reverse rotation or faulty compressor
No time/date
configured,
software failure, or MBB
failure
Software failure or MBB failure
Software failure or MBB failure
Software failure or MBB failure
Software failure or MBB failure
Circuit has 3 strikes or has been locked out by
another alarm
Circuit has 1 strike or has been locked out by another
alarm
See Legend on next page
29

Advertisement

Table of Contents
loading

This manual is also suitable for:

48pd0550pd0648pd06

Table of Contents