Economizer
Control
Board
(ECB)
The ECB controls
the economizer
actuator.
(See Fig. 17 and Table
20.)
The
control
signal
from
the
ECB
uses
either
the
MFT
(Multi-Function
Technology)
digital
communication
protocol
or a
4 to
20
mA
output
signal
as defined
by
the
configuration
Configuration--_ECON--_E.CTL.
The
ECB
has
inputs
for
Indoor Air Quality (IAQ),
Outdoor
Air Quality (OAQ),
enthalpy
and RH sensor.
It also controls
two power exhaust
outputs.
By
digitally
communicating
with
the
ECB,
the
economizer
actuator
is able to provide
the
damper
position
and
diagnostic
information
to
the
ComfortLink
controller.
The
damper
position
is displayed
at Outputs-->ECON-->EC.4P.
Diagnostic
information
is displayed
via Alert
T414.
More
information
about
these alarms is contained
in the Alarms
and Alerts section.
IMPORTANT:
The Economizer
Control
Board
(ECB)
has a
4-position
DIP switch
that is factory
set to '0' (ON, towards
the center of the board).
Do not change
this setting.
RED LED
GREEN LED-LEN
STATUS
(LOCAL EQUIPMENT
NETWORK)
+0+0
C 07027
Fig. 17 - Economizer
Control
Board
(ECB)