APPENDIX
B - VFD INFORMATION
On 48/50PD
units, the supply fan speed is controlled
by a 3-phase
VFD.
The VFD
is located
in the supply
fan section
behind
an
indoor
fan scroll.
The VFD
speed
is controlled
directly
by the
ComfortLink
TM
controls
through
a 0-10Vdc
signal
based
on a
space
temperature
sensor.
The VFD has a display,
which
can be
used for service
diagnostics,
but setup of the control
is to be done
through
the scrolling
marquee
display.
The
VFD
is
powered
during
normal
operation
to
prevent
condensation
from forming
on the boards
during
the off mode and
is stopped
by driving
the speed to 0 (by sending
a 0Vdc signal to
the VFD).
The units use ABB
VFDs.
The interface
wiring
for the
VFDs
is shown
in
the
figure
below.
The
VFD
connects
to
ComfortLink
through
a 0-10Vdc
output
on the
AUXI
board.
Terminal
designations
are shown in the Terminal
Designation
table.
Configurations
are shown
in the VFD Configurations
table.
Table 39 -- VFD TERMINAL
DESIGNATIONS
TERMINAL
FUNCTION
U1
V1
W1
Three-Phase
main circuit input power supply
U2
V2
Three-Phase
AC output to motor, 0V to maximum input
W2
voltage level
X1-11
(GND)
Xl - 12 (COMMON)
Factory-supplied
jumper
Xl - 10 (24VDC)
Xl - 13 (DI- 1)
Run (factory-supplied
jumper)
Xl -10
(24VDC)
Start Enable 1 (factory-supplied
jumper).
When opened,
Xl -16
(DI-4)
the drive goes to emergency stop
X1-2 (AI- 1)
X1-3 (AGND)
Factory wired for 0-10Vdc
remote input
TERMINAL
Xl
O
'
Z
"_"
Z
O
....
o0
_
Co _
04
_
_
E
5
<
+
CO
O
£3
ZS] ZZ
I
m
0-10Vdc signal
from
Comfort
Link
Fig. 40 - VFD Wiring
(08674
81

Advertisement

Table of Contents
loading

This manual is also suitable for:

48pd0550pd0648pd06

Table of Contents