Carrier 50PD05 Operating And Service Instructions page 36

Single package displacement ventilation or single zone variable airflow rooftop units electric cooling/gas heating with puron (r-410a) refrigerant and comfortlink 1.x controls
Hide thumbs Also See for 50PD05:
Table of Contents

Advertisement

Table
13 --
IGC
Board
LED
Alarm
Codes
LED
ACTION
TAKEN
BY
FLASH
DESCRIPTION
RESET
METHOD
PROBABLE
CAUSE
CONTROL
CODE
On
Normal
Operation
__
__
__
Off
Hardware
Failure
No gas heating.
--
Loss of power to the IGC. Check 5 amp fuse on
IGC, power to unit, 24V circuit
breaker, transformer,
and wiring
to the IGC.
1 Flash
Indoor Fan On/Off Delay
5 seconds
subtracted
from
Power reset.
High temperature
limit switch
opens
during
heat
Modified
On delay,
exchanger
warm-up
period
before fan-on delay
5 seconds
added
to Off
expires.
delay
(3 min max).
High temperature
limit switch
opens
within
10 minutes
of heat call (W) Off.
See Limit Switch
Fault.
2 Flashes
Limit Switch
Fault
Gas valve and igniter Off.
Limit switch
closed,
or
High temperature
limit switch
is open.
Check the
Indoor fan and inducer On.
heat call (W) Off.
operation
of the indoor (evaporator)
fan motor.
Ensure that the supply-air
temperature
rise is within
the range on the unit nameplate.
Check wiring
and
limit switch
operation.
3 Flashes
Flame Sense Fault
Indoor fan and inducer On.
Flame sense normal.
The IGC sensed
a flame when the gas valve should
Power reset for LED reset,
be c!osed.
Check wiring, flame
sensor, and gas
valve operation.
4 Flashes
Four Consecutive
Limit Switch
No gas heating.
Heat call (W) Off.
4 consecutive
limit switch
faults within
a single
call
Fault
Power reset for LED reset,
for heat. See Limit Switch
Fault.
5 Flashes
Ignition
Fault
No gas heating.
Heat call (W) Off.
Unit unsuccessfully
attempted
ignition for 15 minutes.
Power reset for LED reset.
Check igniter and flame sensor electrode
spacing,
gaps, etc. Check flame sense and igniter wiring.
Check gas valve operation
and gas supply.
6 Flashes
Induced
Draft Motor Fault
If heat off: no gas heating.
Inducer
sense normal,
or
Inducer
sense On when
heat call Off, or inducer
If heat on: gas valve Off
heat call (W) Off.
sense Off when
heat call On. Check wiring, voltage,
and inducer On.
and operation
of IGC motor. Check speed sensor
wiring
to IGC.
7 Flashes
Rol!out Switch
Lockout
Gas valve and igniter Off.
Power reset.
Rollout
switch
has opened.
Check gas valve
Indoor fan and inducer On.
operation.
Check
induced-draft
blower whee!
is
properly
secured
to motor shaft.
8 Flashes
Internal
Control
Lockout
No gas heating.
Power reset.
IGC has sensed
internal hardware
or software
error.
If fault is not cleared
by resetting
24 v power,
replace
the IGC.
9 Flashes
Temporary
Software
Lockout
No gas heating.
1 hour auto reset, or
Electrical
interference
is disrupting
the IGC
3ower reset,
software.
LEGEND
IGC
- Integrated
Gas [7nit Control
LED
- Light-Emitting
Diode
NOTES:
1. There
is a 3-second
pause
between
alarm
code
displays.
2. If more
than
one alarm
code
exists,
all applicable
alarm
codes
will be displayed
in numerical
sequence.
3. Alarm
codes
on the IGC
will be lost if power
to the unit is interrupted.
Table
14 -- Electric
Heat
Service
Analysis
PROBLEM
Heat Will Not Turn On.
CAUSE
Unit is not configured for heat.
Active alarm.
No power to unit.
Unit is in minimum
heat off-time,
or minimum
cool-
heat changeover
time.
Heat forced
off in Service Test.
No 24 vac at heater contactor.
Open temperature
limit switch
on heater.
Dirty air filters.
Bad heater elements.
Inadequate
Heating.
Occupancy
schedule
set point set too low.
Heat undersized
for load.
Restricted
or low airflow.
Too much
outdoor
air.
Limit switch
cycles
heaters.
Heat Will
Not Turn Off,
Unit is in minimum
heat on-time.
Occupancy
schedule
set point still calling for
Heating.
LEGEND
SAT
Supply Air Temperature
REMEDY
Check heating
configurations
using ComfortLink
_
Scrolling
Marquee.
Check active alarms using ComfortLink
T,, Scrolling
Marquee.
Check power supply, fuses, wiring,
and circuit
breakers.
Check using ComfortLink
_' Scrolling
Marquee.
Check using ComfortLink
_' Scrolling
Marquee.
Turn
Service Test mode off.
Check transformer,
circuit
breaker, auto-reset
limit
switches
on heater, and manual-reset
limit switches
(LS)
on indoor
fan housing.
Check minimum
airflow. Check limit switch
when it is cool,
replace
if not.
Replace air filters.
Power off unit and remove high voltage
wires.
Check
resistance
of element,
replace
if open.
Check setpoints
and adjust
if necessary.
Decrease
load or increase
size of heater.
Remove
restriction,
verify proper fan speed operation,
and
check
SAT compared
to the SAT heating
limits.
Check economizer
position
and configuration.
Adjust
minimum
position
if needed
using ComfortLink
_' Scrolling
Marquee.
Verify proper fan speed operation.
Check rotation
of blower, temperature
rise of unit, and
minimum
airflow. Adjust
as needed.
Check using ComfortLink
_' Scrolling
Marquee.
Check using ComfortLink
_' Scrolling
Marquee.
Unit running
in Service Test mode.
Check using ComfortLink
_' Scrolling
Marquee.
Heater contactor
failed.
Power off unit. Check contactor
and replace
if closed.
36