Carrier 50PD05 Operating And Service Instructions page 73

Single package displacement ventilation or single zone variable airflow rooftop units electric cooling/gas heating with puron (r-410a) refrigerant and comfortlink 1.x controls
Hide thumbs Also See for 50PD05:
Table of Contents

Advertisement

ITEM
CONFIGURATION
DISP
METR
LANG
PROT
PSWD
TEST
UNIT
S.DLY
OC.FN
IDF.F
FS.MX
FS.MN
FS.VM
FN.SW
FL.SW
FS.SW
RM.SW
RH.S
RH.SW
TCS.C
TCS.H
COOL
MIN.C
FS.CD
MRT.C
MOT.C
RST.C
FOD.C
CS.A1
C.LO
ALM.N
SAT
SASP
SA.MU
SA.MD
SAT.U
SAT.L
SST
SSZO
SSZ1
SSZ2
SSZ3
PSI.D
OFC
1 .MXP
2.MNP
2.ON
2.OFF
APPENDIX
A - LOCAL
DISPLAY AND CCN TABLES
(CONT)
Table 34 -- MODE
- CONFIGURATION
EXPANSION
Display
Configuration
Metric
Display
Language
Selection
Password
Enable
Service
Password
Test Display
LEDs
Unit Configuration
Startup
Delay
Fan On When
Occupied
Shut Down on IDF Failure
Supply
Fan Maximum
Speed
Supply
Fan Minimum
Speed
Vent Mode
Fan Speed
Fan Status
Switch
Filter Status
Switch
Fire Shutdown
Switch
Remote
Occupancy
Switch
RH Sensor
on OAQ Input
Space
Humidity
Switch
Temp Cmp
Strt Cool Factr
Temp Cmp
Strt Heat Factr
Cooling
Configuration
Min Compressor
Capacity
Fan Speed
Control
Demand
Compressor
Min On Time
Compressor
Min Off Time
Runtime
to Reset Strikes
Fan-off
Delay, Mech Cool
Current
Sensing
A1
Compressor
Lockout
Temp
Alert
Each Strike
Supply
Air Temperature
Cool Supply
Air Setpoint
SASP Maximum
Reset Up
SASP Maximum
Reset
Down
Minimum
SAT Upper
Level
Minimum
SAT Lower
Level
Low Suction
Control
Suction
OK Temperature
Low Suction
-
Level 1
Low Suction
-
Level 2
Low Suction
-
Level 3
Ckt A Minimum
Pressure
Outdoor
Fan Control
Fan Levl
Max Pressure
Fan Lev2 Min Pressure
Fan Lev2 On Temperature
Fan Lev2 Off Temperature
RANGE
UNITS
DEFAULT
On/Off
Off
0=English
0
1 =Spanish
2=French
3=Portuguese
Enable/Disable
Disable
0000 to 9999
1111
On/Off
Off
0 to 600
Yes/No
Yes/No
80 to 100
10to
40
40 to 100
0=No
Switch
1 =Normal
Open
2=Normal
Closed
0=No
Switch
1 =Normal
Open
2=Normal
Closed
0=No
Switch
1 =Normal
Open
2=Normal
Closed
0=No
Switch
1 =Normal
Open
2=Normal
Closed
Yes/No
0=No
Switch
1 =Normal
Open
2=Normal
Closed
0 to 60
0 to 60
15to
80
1 to 9.9
120 to 999
300 to 999
120 to 999
0 to 600
Enable/Disable
0 to 100F
Yes//No
45 to 75
0 to 20
-20
to 0
35.0 to 65.0
35.0 to 65.0
10to
50
10to
50
5 to 50
0 to 50
0 to 500
100 to 500
100 to 500
0to
100
0to
100
%
%
^F
mins
mins
%
^F
sec
sec
sec
sec
dF
dF
^F
^F
dF
dF
dF
dF
dF
dF
psig
psig
psig
F
F
30
Yes
Yes
100
2O
5O
0: no FlOP
1: FlOP
0: no FlOP
1: FlOP
0: no FlOP
1: FlOP
0
No
0
7O
3
18O
3OO
3OO
6O
Disable:
reserved
for
future
use
DO NOT ENABLE
0
Yes
65
10
-10
6O
45
18
2O
15
10
2O
450
200
55
45
CON
TABLE/SUB-TABLE
SERVICE
CONFIGURATION
DISPLAY
(display
only,
not in
table)
UNIT
COOL
CFG
CCN POINT
DISPUNIT
LANGUAGE
PASS
EBL
PASSWORD
DISPTEST
STARTDLY
OCC
FAN
FATALFAN
SPEEDMAX
SPEEDMIN
SPEEDVNT
FANSTCFG
FILSTCFG
SHTDNCFG
REMOCCFG
RH OAQ
HUMSTCFG
TCSTCOOL
TCSTHEAT
MIN CAPC
SPEEDDMD
MIN ON
MIN OFF
MIN ON
S
COOL
FOD
A1 SENSE
OATLCOMP
ALM
NOW
SASP
SASPMAXU
SASPMAXD
SATMIN
H
SATMIN
L
SSTOK
SSTLEV1
SSTLEV2
SSTLEV3
DELTAP
A
LEV1MAXP
LEV2MINP
LEV2ON
LEV2OFF
PAGE
NO.
12
12
12
12
12
12
12
12
12
12
12
12
12
13
13
13
13
14
17
24
25
24
17
18
18
26
26
26
26
26
15
15
15
15
73