APPENDIX
B - VFD INFORMATION
(CONT)
Main Fan Replacement
The main cooling
fan of the VFD has a life span of about 60,000
operating
hours at maximum
rated operating
temperature
and drive
load. The expected
life span doubles
for each 18 F drop in the fan
temperature
(fan temperature
is a function
of ambient
temperatures
and drive loads).
Fan
failure
can be predicted
by the
increasing
noise
from
fan
bearings
and the gradual
rise in the heat sink temperature
in spite of
heat sink cleaning.
If the drive
is operated
in a critical
part of a
process,
fan replacement
is recommended
once
these
symptoms
2
start appearing.
Replacement
fans are available
from Carrier.
To replace
the main fan for frame sizes RI through
R2, perform
the
following
(see Main Fan Replacement
figure):
1. Remove
power
from drive.
2. Remove
drive cover.
3. For frame sizes RI and R2, press together
the retaining
clips
on the fan cover
and lift.
4. Disconnect
the fan cable.
5. Install the new fan by reversing
Steps 2 to 4.
6. Restore
power.
Fig. 43 - Main
Fan Replacement
(Frame
Sizes R1-R2)
(08681
Control
Panel
Cleaning
Use
a soft damp
cloth to clean
the control
panel.
Avoid
harsh
cleaners which
could scratch the display
window.
Battery Replacement
A battery
is only used in assistant control
panels that have the clock
function
available
and
enabled.
The
battery
keeps
the
clock
operating
in memory
during
power
interruptions.
The expected
life
for the battery
is greater
than ten years. To remove
the battery,
use
a coin to rotate the battery
holder on the back of the control
panel.
Replace
the battery
with type CR2032.