Carrier 50PD05 Operating And Service Instructions page 54

Single package displacement ventilation or single zone variable airflow rooftop units electric cooling/gas heating with puron (r-410a) refrigerant and comfortlink 1.x controls
Hide thumbs Also See for 50PD05:
Table of Contents

Advertisement

Integrated
Gas Control
(IGC) Board
The IGC is provided
on gas heat units. (See Fig. 21 and Table 24.)
The IGC controls
the direct spark ignition
system
and monitors
the
rollout
switch,
limit
switch,
and induced-draft
motor
Hall Effect
switch.
The
IGC
is equipped
with
an LED
(light-emitting
diode)
for
diagnostics.
See the Troubleshooting
section for more information.
RED LED-STATUS
LH33WPOO2A
II
II
II
1068-12
Fig. 21 - Integrated
Gas Control
(IGC)
Board
( 07028
Table 24 -- IGC Connections
TERMINAL
CONNECTION
LABEL
POINT DESCRIPTION
SENSOR LOCATION
TYPE OF I/O
PIN NUMBER
INPUTS
RT, C
Input power from TRAN 1
control box
24 VAC
SS
Speed sensor
gas section
analog input
J1, 1-3
FS, T1
Flame sensor
gas section
switch input
W
Heat stage 1
MBB
24 VAC
J2, 2
RS
Rollout switch
gas section
switch input
J2, 5-6
LS
Limit switch
gas section
switch input
J2, 7-8
CS
Centrifugal switch (not used)
switch input
J2, 9-10
OUTPUTS
L1, CM
Induced draft combustion
motor
gas section
line VAC
IFO
Indoor fan request
control box
relay
J2, 1
GV (W1)
Gas valve (heat stage 1)
gas section
relay
J2, 12
GV (W2)
Gas Valve (heat stage 2, from MBB)
gas section
Not on IGC
54