Carrier 50PD05 Operating And Service Instructions page 32

Single package displacement ventilation or single zone variable airflow rooftop units electric cooling/gas heating with puron (r-410a) refrigerant and comfortlink 1.x controls
Hide thumbs Also See for 50PD05:
Table of Contents

Advertisement

measured
atemperature
above 268 F(131 C)orthe thermistor
has
short circuited (jumpered
out).
The DSC willde-energize
the compressor
contactor
and unloader
solenoid, and thealarm relay c ontacts
will close c ausing aT051
alert o ntheComfortLink Control. Thecompressor
will be
allowed torestart after 3 0minute delay a nd after t he DTTreads
below 250 F(120 C). T he flash code a nd alarm relay c ontacts
will
bereset after t he compressor
has runfor60minutes without any
other A LERTs. I f five discharge
temperature
ALERTs have
occurred
within four h ours, the DSC willlock out t he compressor.
The lockout can only bereset bycycling the 24VAC p ower offand
on.
Flash
Code 3 -- Compressor
Protector
Trip
This occurs
when
the demand
signal from the system
controller
is
greater than 1.44VDC
and there is no compressor
current
detected.
This could
be due to the compressor's
internal
overload
protector
being
open,
fuse
or
breaker
open,
power
disconnected
to
compressor
contactor,
compressor
power
wiring
not run through
DSC
current
transformer
port
or a compressor
contactor
failure.
The DSC will de-energize
the compressor
contactor
and unloader
solenoid
and the alarm relay contacts
will close
causing
a T051
alert on the ComfortLink
Control.
The DSC will wait for the two
minute
anti-short
cycle
timer
to
time
out
and
if the
system
controller
demand
signal is still greater
than 1.44VDC,
energize the
compressor
contactor
again.
If compressor
current
is detected
on
the restart,
the ALERT
code and alarm relay output will reset. The
DSC
will
attempt
to restart
compressor
as long
as the
system
controller
demand
is above
1.44VDC.
There
is no lockout
feature
for this ALERT.
Flash
Code 4 -- Locked
Rotor
A locked
rotor condition
in the compressor
is sensed
by the DSC
on four
consecutive
start
ups.
The
DSC
will
de-energize
the
compressor
contactor
and unloader
solenoid
and the alarm
relay
contacts
will
close
causing
a T051
alert
on the
ComfortLink
Control.
This code
results
in a lockout
and can only be reset by
cycling
the 24VAC power
off and on.
Flash Code 5 -- Demand
Signal Loss
This
occurs
when
the demand
signal
input
has
dropped
below
0.5VDC.
The demand
input
signal
wire may be disconnected
or
the system
controller
providing
the signal may not be powered.
The DSC will de-energize
the compressor
contactor
and unloader
solenoid
and the alarm
relay contacts
will close causing
a T051
alert on the ComfortLink
Control.
Once
the system
controller
demand
signal
input
has risen above
0.5VDC,
the ALERT
code
and alarm
relay output
will reset. If the demand
signal
is above
1.44VDC
and
the
anti-short
cycle
timer
has
timed
out,
the
compressor
will restart.
Flash
Code 6 -- Discharge
Thermistor
Fault
This
occurs
when
the
DSC
is not receiving
a signal
from
the
discharge
temperature
thermistor
(DTT).
The thermistor
may be
missing,
disconnected
or a wire broken.
The alarm relay contacts
will
close
and
the
DSC
will
not increase
the
capacity
of the
compressor
beyond
50%
loading.
This
ALERT
code
and alarm
relay output are reset by reconnecting
the DTT.
Flash
Code 7 --Reserved
for future use
Flash
Code 8 --
Compressor
Contactor
Fault
This
occurs
when
the compressor
current
is detected
when
the
system
controller
demand
signal
is
below
1.44VDC.
The
compressor
contactor
may
have welded
contacts
or the contacts
may be mechanically
jammed.
The compressor
will continue
to run
in
this
condition
since
the
DSC
cannot
open
the
compressor
contactor.
The DSC will energize
the compressor
contactor
and the
alarm
relay
contacts
will
close
causing
a T051
alert
on the
ComfortLink
Control.
The
unloader
solenoid
will
remain
energized
causing
the compressor
to run unloaded
as long
as the
system
controller
demand
signal
is less than
1.44VDC.
If the
system
controller
demand
is greater
than
1.44VDC,
the unloader
solenoid
will de-energize
causing
the compressor
to run loaded.
The ALERT
code and alarm relay output are reset when
current is
no longer
detected
while
system
controller
demand
signal is below
1.44VDC.
Flash
Code 9 -- Low 24VAC
Supply
This
occurs
when
the supply
voltage
to the DSC
has dropped
below
18.5VDC.
The
DSC
will
de-energize
the
compressor
contactor
and unloader
solenoid.
The alarm
relay contacts
may
close
if the voltage
is high enough
for the alarm relay to pull in.
The ALERT
code and alarm relay output are reset when the supply
voltage
to the DSC rises above 19.5VAC.
Table 10 -- DSC Red LED
Flash Codes
LED Flash
Description
Action Taken
Reset
Probable Cause
Code
by Control
Method
1
Reserved for Future Use
N/A
N/A
N/A
Flash
2
High Discharge Temperature
Compressor
Automatic
Compressor discharge temperature
is greater then 268
Flash
shutdown
degrees F or the DTT is shorted.
3
Compressor
Protector Trip
Compressor
Automatic
Compressor's
internal overload protector being open,
Flash
shutdown
fuse or breaker open, power disconnected
to compres-
sor contactor, compressor
power wiring not run through
DSC current transformer port or a compressor
contactor
failure.
4
Locked Rotor
Compressor
Manual
Four consecutive start ups with locked rotor.
Flash
lockout
5
Demand Signal Loss
Compressor
Automatic
Signal wire may be disconnected
or the system control-
Flash
shutdown
ler providing the signal may not be powered
6
Discharge Thermistor
Fault
Capacity Limited
Automatic
DTT may be missing, disconnected
or a wire broken
Flash
7
Reserved for Future Use
N/A
N/A
N/A
Flash
8
Compressor
Contactor Fault
Keep capacity
Automatic
Compressor contactor may have welded contacts or the
Flash
at 15%
contacts may be mechanically
jammed
9
Low 24VAC Supply
Compressor
Automatic
Bad connection or transformer.
Flash
shutdown
32