AIRFLOW
(Cfm)
1500
1600
1700
1800
1900
2000
2100
2200
2300
2400
2500
AIRFLOW
(Cfm)
1500
1600
1700
1800
1900
2000
2100
2200
2300
2400
2500
LEGEND
Bhp - Brake Horsepower
AIRFLOW
(Cfm)
1500
1600
1700
1800
1900
2000
2100
2200
2300
2400
2500
AIRFLOW
(CFM)
1500
1600
1700
1800
1900
2000
2100
2200
2300
2400
2500
LEGEND
Bhp - Brake Horsepower
Rpm
607
634
662
690
719
748
777
807
837
867
897
Table 48 -- Fan
Performance
- 48PDE06
Vertical
Units
0.2
Bhp
0.29
0.33
0.39
0.45
0.51
0.59
0.67
0.75
0.85
0.95
1.06
Rpm
7OO
724
748
773
799
825
852
879
9O7
935
963
AVAILABLE
EXTERNAL STATIC PRESSURE
0.4
0.6
(in. wg)
Bhp
0.38
0.43
0.49
0.55
0.63
0.70
0.79
0.88
0.98
1.09
1.21
Rpm
784
8O4
826
848
872
896
92O
946
971
998
1024
Bhp
0.47
0.53
0.60
0.67
0.74
0.83
0.92
1.01
1.12
1.24
1.36
Rpm
861
879
898
918
94O
962
985
1008
1032
1057
1082
0.8
Bhp
0.57
0.64
0.71
0.78
0.86
0.95
1.05
1.15
1.26
1.38
1.51
Rpm
1004
1017
1032
1048
1066
1084
1104
1124
1145
1167
1189
1.2
Bhp
0.79
0.86
0.94
1.02
1.11
1.21
1.31
1.43
1.55
1.68
1.82
Rpm
1070
1081
1094
1109
1125
1142
1160
1179
1198
1219
1240
AVAILABLE
EXTERNAL STATIC PRESSURE
(in. wg)
1.4
1.6
Bhp
0.91
0.98
1.06
1.15
1.24
1.35
1.45
1.57
1.70
1.83
1.97
Rpm
1133
1143
1155
1168
1182
1197
1214
1231
1250
1269
1290
NOTES:
Bhp
Rpm
1.03
1194
1.11
1203
1.19
1213
1.28
1224
1.38
1237
1.49
1251
1.60
1267
1.72
1283
1.85
1300
1.99
1318
2.14
1337
i. Maxinnml continuous
BHP is 2.0.
2. See General Fan Performance
Notes.
1.8
Bhp
1.15
1.24
1.32
1.42
1.52
1.63
1.75
1.87
2.01
2.15
2.30
Rpm
62O
648
677
7O7
737
767
798
829
861
893
925
Rpm
1013
1027
1043
1060
1078
1098
1119
1140
1163
1186
1210
0.2
Bhp
0.30
0.35
0.40
0.47
0.54
0.61
0.70
0.79
0.89
1.00
1.12
1.2
Bhp
0.81
0.88
0.96
1.05
1.14
1.24
1.35
1.47
1.60
1.73
1.88
Table
49 -- Fan Performance
- 48PDF06
Vertical Units
Rpm
711
736
762
788
815
843
871
9OO
929
959
989
AVAILABLE
EXTERNAL STATIC PRESSURE
0.4
0.6
Bhp
0.39
0.45
0.51
0.58
0.65
0.73
0.82
0.92
1.03
1.15
1.27
Rpm
794
816
838
862
887
912
938
965
992
1020
1048
Bhp
0.49
0.55
0.61
0.69
0.77
0.85
0.95
1.05
1.17
1.29
1.42
(in. wg)
0.8
Rpm
871
89O
910
931
954
977
1001
1026
1052
1078
1105
Rpm
1078
1091
1105
1120
1137
1155
1174
1195
1216
1238
1261
AVAILABLE
EXTERNAL STATIC PRESSURE
(in. wg)
1.4
1.6
Bhp
0.92
1.00
1.08
1.18
1.27
1.38
1.49
1.62
1.75
1.89
2.04
Rpm
1141
1152
1165
1179
1194
1210
1228
1247
1267
1288
1309
NOTES:
Bhp
Rpm
1.05
1202
1.13
1211
1.21
1222
1.31
1235
1.41
1249
1.52
1264
1.64
1280
1.77
1298
1.90
1317
2.05
1336
2.20
1357
i. Maxinnml continuous
BHP is 2.0.
2. See General Fan Performance
Notes.
1.8
Bhp
0.59
0.65
0.72
0.80
0.89
0.98
1.08
1.19
1.31
1.43
1.57
Bhp
1.17
1.25
1.35
1.44
1.55
1.67
1.79
1.92
2.06
2.21
2.37
1.0
Rpm
Bhp
934
0.68
950
0.75
967
0.82
985
0.90
1004
0.98
1024
1.08
1045
1.18
1067
1.29
1090
1.40
1113
1.53
1137
1.66
2.
Rpm
Bhp
1253
1.28
1260
1.37
1269
1.46
1279
1.56
1291
1.66
1304
1.78
1318
1.90
1333
2.03
1349
2.17
1366
2.31
1.0
Rpm
Bhp
944
0.70
960
0.76
978
0.84
997
0.92
1017
1.01
1039
1.11
1061
1.21
1084
1.33
1108
1.45
1133
1.58
1158
1.72
2.0
Rpm
Bhp
1260
1.30
1269
1.39
1278
1.48
1290
1.59
1302
1.70
1316
1.81
1331
1.94
1348
2.08
1365
2.22
1384
2.37
93