Carrier 50PD05 Operating And Service Instructions page 101

Single package displacement ventilation or single zone variable airflow rooftop units electric cooling/gas heating with puron (r-410a) refrigerant and comfortlink 1.x controls
Hide thumbs Also See for 50PD05:
Table of Contents

Advertisement

Model Number:
Serial Number:
Date:
Technician:
Control Type:
Set Points:
CONTROL
SET POINT
AND
CONFIGURATION
LOG
Software Versions:
MBB:
CESR131320--
ECB:
CESRI31249--
MAR@
CESRI31171--
INDICATE
UNIT
SETTINGS
BELOW
Thermostat/T55
Space Temp./T-56
Space Temp./T-58
Space Temp.
Cooling
Occupied:
Unoccupied:
Heating
Occupied:
Unoccupied:
ITEM
CONFIGURATION
DISP
METR
LANG
PROT
PSWD
TEST
UNIT
S.DLY
OC.FN
IDF.F
FS.MX
FS.MN
FS.VM
FN.SW
FL.SW
FS.SW
RM.SW
RH.S
RH.SW
TCS.C
TCS.H
COOL
MIN.C
FS.CD
MRT.C
MOT.C
RST.C
FOD.C
CS.A1
C.LO
ALM.N
SAT
SASP
SA.MU
SA.MD
SAT.U
SAT.L
SST
SST.O
SST.1
SST.2
SST.3
PSI.D
OFC
1.MXP
2.MNP
2.ON
2.OFF
Table 65 -- MODE
- CONFIGURATION
EXPANSION
Display
Configuration
Metric Display
Language
Selection
Password
Enable
Service
Password
Test Display
LEDs
Unit Configuration
Startup Delay
Fan On When Occupied
Shut Down on IDF Failure
Supply
Fan Maximum
Speed
Supply
Fan Minimum
Speed
Vent Mode
Fan Speed
Fan Status Switch
Filter Status Switch
Fire Shutdown
Switch
Remote Occupancy
Switch
RH Sensor on QAQ Input
Space Humidity
Switch
Temp Cmp Strt Cool Factr
Temp Crop Strt Heat Factr
Cooling
Configuration
Min Compressor
Capacity
Fan Speed
Control
Demand
Compressor
Min On Time
Compressor
Min Off Time
Runtime to Reset Strikes
Fan-off
Delay, Mech Cool
Current Sensing
A1
Compressor
Lockout
Temp
Alert Each Strike
Supply Air Temperature
Cool Supply
Air Setpoint
SASP Maximum
Reset Up
SASP Maximum
Reset
RANGE
UNITS
DEFAULT
On/Off
Off
0=English
0
1=Spanish
2=French
3 = Portuguese
Enable/Disable
Disable
0000 to 9999
1111
On/Off
Off
0 to 600
sec
30
Yes/No
Yes
Yes/No
Yes
80 to 100
%
100
10 to 40
%
40to
100
^F
O=No Switch
1=Normal
Open
2=Normal
Closed
O=No Switch
1=Normal
Open
2=Normal
Closed
O=No Switch
1=Normal
Open
2=Normal
Closed
O=No Switch
O
1=Normal
Open
2=Normal
Closed
Yes/No
No
0=No
Switch
0
1=Normal
Open
2=Normal
Closed
0 to 60
mins
0
0 to 60
mins
0
2O
5O
0: no FlOP
1: FlOP
0: no FlOP
1: FlOP
0: no FlOP
1: FlOP
15 to 80
%
70
1 to 9,9
^ F
3
120 to 999
sec
180
300 to 999
sec
300
120 to 999
sec
300
0 to 600
sec
60
Enable/Disable
Disable: reserved
for
future use
DO NOT ENABLE
0 to 100F
dF
0
Yes//No
Yes
45 to 75
dF
65
0 to 20
^ F
10
-20
to 0
^ F
-10
CCN
TABLE/SUB-TABLE
SERVICE
CONFIGURATION
DISPLAY
(display only, not in
table)
UNIT
COOL
CFG
CCN POINT
DISPUNIT
LANGUAGE
PASS EBL
PASSWORD
DISPTEST
STARTDLY
OCC
FAN
FATALFAN
SPEEDMAX
SPEEDMIN
SPEEDVNT
FANSTCFG
FILSTCFG
SHTDNCFG
REMOCCFG
RH OAQ
HUMSTCFG
TCSTCOOL
TCSTHEAT
MIN CAPC
SPEEDDMD
MIN ON
MIN OFF
MIN ON S
COOL
FOD
A1 SENSE
OATLCOMP
ALM
NOW
SASP
SASPMAXU
SASPMAXD
Down
Minimum
SAT Upper Level
Minimum
SAT Lower Level
Low Suction
Control
Suction
OK Temperature
Low Suction
- Level 1
Low Suction
- Level 2
Low Suction
- Level 3
Ckt A Minimum
Pressure
Outdoor
Fan Control
Fan Levl Max Pressure
Fan Lev2 Min Pressure
Fan Lev2 On Temperature
Fan Lev2 Off Temperature
35.0 to 65.0
dF
60
35.0 to 65.0
dF
45
10 to 50
dF
18
10 to 50
d F
20
5 to 50
dF
15
0 to 50
dF
10
0 to 500
psig
20
100 to 500
psig
450
100 to 500
psig
200
0 to t00
F
55
0 to 100
F
45
SATMIN
H
SATMIN
L
SSTOK
SSTLEV1
SSTLEV2
SSTLEV3
DELTAP A
LEVlMAXP
LEV2MINP
LEV2ON
LEV2OFF
ENTRY
101