Carrier 50PD05 Operating And Service Instructions page 99

Single package displacement ventilation or single zone variable airflow rooftop units electric cooling/gas heating with puron (r-410a) refrigerant and comfortlink 1.x controls
Hide thumbs Also See for 50PD05:
Table of Contents

Advertisement

GENERAL
NOTES
FOR FAN PERFORMANCE
DATA TABLES
1, Static
pressure
losses
from
accessories
and
options
(economizer,
etc.) must be added to external
static pressure
before
entering
Fan
Performance
table,
Refer
to
Accessory/FIOP
Static Pressure
information,
2. Interpolation
is permissible,
Do not extrapolate.
3, Fan performance
tables
are based on wet coils, clean filters,
and casing losses,
Gas heat losses are included
for 48 series
units,
4. Extensive motor and drive testing on these units ensures
that the full horsepower range of the motor can be utilized
with confidence, Using the fan motors up to the bhp rating
shown will not result in nuisance tripping or premature
motor failure, Unit warranty will not be affected,
5. Use of a field-supplied
motor
may affect wire size.
Recalculate the unit power supply MCA and MOCP if
required. Contact your Carrier representative for details.
6. Use the following formula to calculate input watts:
Input Watts = Bhp x (746/Motor Eft)
99