Programming Operating Schedules; Service Test; Independent Outputs; Fan Test - Carrier 50PD05 Operating And Service Instructions

Single package displacement ventilation or single zone variable airflow rooftop units electric cooling/gas heating with puron (r-410a) refrigerant and comfortlink 1.x controls
Hide thumbs Also See for 50PD05:
Table of Contents

Advertisement

Programming
Operating
Schedules
The
ComfortLink
_
controls
will
accommodate
up
to
eight
different
schedules
(Periods
1 through
8), and each schedule
is
assigned
to the desired
days of the week.
Each schedule
includes
an occupied
on and off time. As an example,
to set an occupied
schedule
for 8 AM to 5 PM for Monday
through
Friday,
the user
would
set days Monday
through
Friday
to ON for Period
1. Then
the user would
configure
the Period
1 Occupied
From
point
to
08:00
and the Period
1 Occupied
To point
to 17:00. To create
a
different
weekend
schedule,
the user would
use Period
2 and set
days Saturday
and Sunday
to ON with
the desired
Occupied
On
and Off times.
IMPORTANT:
By
default,
the
time
schedule
periods
are
programmed
for 24 hours of occupied
operation.
To create a schedule,
perform
the following
procedure:
1. Scroll
to
the
Configuration
mode,
and
select
CCN
CONFIGURATION
(CCN).
Scroll
down
to the Schedule
Number
(Configuration--,CCN--,SCH.O=SCH_.
If
password
protection
has been
enabled,
the user will
be
prompted
to enter
the password
before
any new
data is
accepted. SCH_
has a range of 0 to 99. The default
value
is 1. A value
of 0 is always
occupied,
and the unit will
control
to its occupied
set points.
A value
of 1 means the
unit will follow
a local
schedule,
and a value
of 65 to 99
means
it will follow
a CCN
schedule.
Schedules
2-64
are
not used
as the
control
only
supports
one
internal/local
schedule.
If one of the 2-64
schedules
is configured,
then
the control will force the number
back to 1. Make sure the
value is set to 1 to use a local schedule.
2. Enter
the Time
Clock
mode.
Scroll down
to the LOCAL
TIME
SCHEDULE
(SCH.L)
sub-mode,
and
press
ENTER.
Period
1 (PER.l)
will be displayed.
3. Scroll
down
to the MON.I
point.
This point
indicates
if
schedule
1 applies
to Monday.
Use the ENTER
command
to go into Edit mode,
and use the Up or Down
key to
change
the display
to YES or NO. Scroll down
through
the
rest of the days
and apply
schedule
1 where
desired.
The
schedule
can also be applied
to a holiday.
4. Configure
the beginning
of the occupied
time period
for
Period
1 (OCC).
Press ENTER
to go into Edit mode,
and
the first two digits
of the 00.00 will start flashing.
Use the
Up or Down
key to display
the correct
value for hours,
in
24-hour
(military)
time.
Press ENTER
and hour value
is
saved
and the minutes
digits
will start flashing.
Use the
same
procedure
to display
and save
the desired
minutes
value.
5. Configure
the unoccupied
time for period
1 (UNC).
Press
ENTER
to go into Edit mode,
and the first two digits
of the
00.00 will start flashing.
Use the Up or Down key to display
the correct
value for hours, in 24-hour
(military)
time. Press
ENTER
and hour value is saved and the minutes
digits will
start flashing.
Use the same
procedure
to display
and save
the desired
minutes
value.
6. The first schedule
is now complete.
If a second
schedule
is
needed,
such as for weekends
or holidays,
scroll
down
and
repeat
the
entire
procedure
for
period
2
(PER.2).
If
additional
schedules
are needed,
repeat
the process
for as
many
as are needed.
Eight
schedules
are provided.
See
Table 4 for an example
of setting the schedule.
SERVICE
TEST
The Service
Test function
can be used to verify proper
operation
of
compressors,
heating
stages,
indoor
fan,
outdoor
fans,
power
exhaust
fans,
economizer,
crankcase
heaters,
and the alarm relay.
Use of Service
Test is recommended
at initial
system
start up and
during
troubleshooting
(See Table 5 for point details).
Service
Test
mode
has
the
following
changes
from
normal
operation:
• Outdoor
air temperature
limits for cooling
circuits,
economizer,
and heating
are ignored.
Normal
compressor
time guards
and
other staging
delays are reduced
to 30 seconds
or less.
• Circuit alerts are limited to 1 strike (versus
3) before changing
to
alarm shut down state.
• The status of ALM.N
is ignored
so all alerts and alarms are
broadcast
on CCN.
• The words
"SERVICE
TEST"
are inserted
into every alarm
message.
Service
test can only be turned
ON/OFF
at the unit display.
Once
turned
ON, other entries may be made with the display
or through
CCN.
To turn Service
Test on, change
the value
of TEST to ON.
To turn service test off, change
the value of TEST to OFF.
IMPORTANT:
Service
Test mode
may be password
protected.
Refer
to Basic
Control
Usage
section
for
more
information.
Depending
on
the
unit
model,
factory-installed
options,
and
field-installed
accessories,
some of the Service
Test functions
may
not apply.
Independent
Outputs
The independent
(INDP)
submenu
is used to change output status
for the economizer,
power
exhaust
stages,
crankcase
heaters,
and
the
alarm
relay.
These
independent
outputs
can
operate
simultaneously
with other Service Test modes. All outputs
return to
normal
operation
when
Service
Test
is turned
off.
When
the
economizer
is using
the
factory
default
Digital
Control
Type
(Configuration---,ECON---,E.CTL
is 1 or 2) then the Economizer
Calibration
feature
may be used to automatically
check
and reset
the economizer
actuator range of motion.
Refer to the economizer
operation
section
of more details.
IMPORTANT:
If a network
force
is applied
to CCN
points:
ECONOCMD,
PE_I,
PE_2,
or ALMOUT,
their respective
test
mode
functions
will not be usable.
Those
forces
are at a higher
level
than test mode;
therefore
they will still be honored
when
in
test mode.
Fan Test
The fans (FANS)
submenu
is used to change
output
status for the
indoor
fan and outdoor
fan stages. The VFD power
can be turned
on and off via IDF
(Supply
VFD
Power
Test).
The indoor
fan
speed
test (F.SPD)
runs the fan at the desired
speed entered.
The
outdoor
fan relay test (OFC.I)
only
tests the relay
for switching
between
high and low speeds.
The actual outdoor
fan will not run
unless
cool test is on.
The cooling
(COOL)
and heating
(HEAT)
service
test outputs
are reset to OFF for the fans service test.
10

Advertisement

Table of Contents
loading

This manual is also suitable for:

48pd0550pd0648pd06

Table of Contents