Cooling Troubleshooting - Carrier 50PD05 Operating And Service Instructions

Single package displacement ventilation or single zone variable airflow rooftop units electric cooling/gas heating with puron (r-410a) refrigerant and comfortlink 1.x controls
Hide thumbs Also See for 50PD05:
Table of Contents

Advertisement

Table
8 -- ComfortLink
T_Alarm
Codes
(cont)
ALARM
OR
ACTION TAKEN BY
RESET
DESCRIPTION
PROBABLE
CAUSE
ALERT
CONTROL
METHOD
NUMBER
T178
Loss of Communication
with the Capacity
Unit shutdown
-HVAC
Automatic
Communication
wiring problem with AUX1 or faulty
Control Board
disable
MBB, ECB, or AUXl
T179
Loss of communication
with the Economizer
No economizer
Automatic
Communication
wiring problem with ECB or faulty
Control Board
operation
MBB, ECB, or AUXl
Loss of communication
with the Economizer
No economizer
T180
Actuator
operation
Automatic
Communication
wiring problem with actuator.
No Linkage Operation
Received a table write from Linkage before, now not
A200
Linkage Timeout
Error - Comm Failure
fall back to local SPT
Automatic
receiving any linked commands
A404
Fire Shutdown
Unit Shutdown
Automatic
Smoke detected
by smoke detector
T408
Dirty Filter
Alert Generated
Automatic
Dirty Filter
If IDF.F =
If IDF.F = Yes, then Unit
YES, then
Fan Status Switch ON, Fan Contactor
OFF
Shutdown
Manual,
Bad Fan Status Switch. Configuration
incorrect.
otherwise
T409
automatic
If IDF.F =
Fan Status Switch OFF, Fan Contactor ON
If IDF.F = Yes, then Unit
YES,Manual,then T ripped Circuit Breaker. Broken belt. Bad indoor fan
Shutdown
otherwise
motor. Configuration
incorrect.
Bad fan status switch.
automatic
Economizer
Damper Actuator Out of
Calibrate economizer
(E.CAL). If problem
still exist
Calibration
Alert Generated
Automatic
then determine
what is limiting economizer
rotation.
Economizer
Damper Actuator Torque Above
Load Limit
Alert Generated
Automatic
Actuator
load too high. Check damper load.
Economizer
Damper Actuator Hunting
Alert Generated
Automatic
Damper position changing
too quickly.
T414
Excessively
No economizer
motion.
Check damper
blades, gears,
Economizer
Damper Stuck or Jammed
Alert Generated
Automatic
and actuator.
Economizer
Damper Actuator Mechanical
Failure
Alert Generated
Automatic
Check actuator
and replace if necessary.
Economizer
Damper Actuator Direction
Switch Wrong
Alert Generated
Automatic
Actuator direction
control switch (CCW, CW) wrong.
Bad sensor, bad wiring, or sensor configured
T415
IAQ Input Out of Range
No IAQ Operations
Automatic
incorrectly.
Bad sensor, bad wiring, or sensor configured
T416
OAQ Input Out of Range
No OAQ Operations
Automatic
incorrectly.
LEGEND
ECB
-
Economizer
ControlBoard
IGC
Integrated Gas Controller
MBB
-
Main Base Board
OAT
-
Outdoor-Air
Thermistor
Cooling
Troubleshooting
Use the Scrolling Marquee display or a CCN device to view the
cooling status display and the cooling diagnostic
display (see
Appendix A) for information on the cooling operation. Check the
current alarms and alarm history for any cooling alarm codes and
correct any causes. (See Table 9.)
Verify any
unique
control
configurations
per installed
site
requirements or accessories. If alarms conditions are corrected and
cleared, operation of the compressors and fans may be verified by
using the Service Test mode. (See Table 5.) See Table 9 for general
cooling service analysis.
30