Carrier 50PD05 Operating And Service Instructions page 26

Single package displacement ventilation or single zone variable airflow rooftop units electric cooling/gas heating with puron (r-410a) refrigerant and comfortlink 1.x controls
Hide thumbs Also See for 50PD05:
Table of Contents

Advertisement

only the outdoor temperature to control the outdoor fans. If both
the SCT and OAT fail, then circuit shutdown alarm will occur also.
The cause of the alert is usually a faulty thernfistor, a shorted or
open thernfistor caused by a wiring error, or a loose connection.
Alert Code T066 - Circuit A Saturated
Suction Temperature
Thermistor
Failure
This alert occurs when the unit's suction transducers are turned off
internally.
Cooling will not operate.
This is usually due to a
network force on a non exposed
CCN point.
Reload factory
defaults or reinstall software on the MBB.
Consult the network
manager if alert continues.
Alert Code T073 - Outdoor Air Temperature
Thermistor
Failure
This alert occurs when the temperature is outside the range -40 ° to
240°F (-40 ° to 116°C). For all units, all ambient temperature
lockout linfits for cooling and heating are ignored. For all units, if
both SCT and OAT fail, then circuit shutdown alarm will also
occur. For econonfizer equipped units, the econonfizer will not
operate to provide cooling. The econonfizer will still operate for
ventilation.
The control will
use condenser
temperatures
for
outdoor fan control. For units with CCH crankcase
heat relay
control, the crankcase
heat relay will be turned
on if any
compressor is off. This alert resets automatically. The cause of the
alert is usually a faulty thernfistor, a shorted or open thernfistor
caused by a wiring error, or a loose connection.
Alert Code T074 - Space Temperature
Thermistor
Failure
This alert occurs when the temperature is outside the range -40 ° to
240°F (-40 ° to 116°C). Cooling and heating will not operate. For
econonfizer equipped units, the econonfizer will still operate for
ventilation. This alert resets automatically. The cause of the alert is
usually a faulty thernfistor in the T-55, T-56, or T-58 device, a
shorted or open thernfistor caused by a wiring error, or a loose
connection.
Alert Code T075 - Supply Air Temperature
Thermistor
Failure
This alert occurs when the temperature is outside the range -40 ° to
240°F (-40 ° to 116°C). Econonfizer
cooling
and compressor
operation cannot occur while this alert is active. The unit will not
be allowed to enter cooling mode. This alert resets automatically.
The cause of the alert is usually a faulty thernfistor, a shorted or
open thernfistor caused by a wiring error, or a loose connection.
Alert Code T076 - Return Air Thermistor
Failure
This alert occurs when the temperature is outside the range -40 ° to
240°F (-40 ° to 116°C). Differential dry bulb crossover control
can not occur. Free cooling can only be controlled by the OAT and
enthalpy.
This alert resets automatically. The cause of the alert is
usually a faulty thernfistor, a shorted or open thernfistor caused by
a wiring error, or a loose connection.
Alert Code T077 - Space Relative Humidity Sensor Failure
This alert occurs when the input is less than 3.5 mA and the sensor
is configured as installed. If a hunfidistat is not installed, then
dehunfidification will not be functional.
Check sensor and wiring.
This alert clears automatically.
IMPORTANT:
An ECB must be installed to use the space
relative hunfidity sensor.
Alert Code T092 - Circuit A Suction Pressure Transducer
Failure
This alert occurs when the board does not properly read the
transducer voltage. A circuit cannot run when this alert is active.
Use the Scrolling Marquee to reset the alarm. The cause of the alert
is usually a faulty transducer, faulty 5-v power supply, or a loose
connection.
Alert Code T102 - Compressor
A1 Current
Sensor Failure
This Alert indicates that Current Sensing A1 (CS.A1) has been
enabled.
The unit does not support the use of a current sensor at
this time.
Change
the CS.A1
to disable and this alert will clear and
not return.
(Con figuration--+COOL--+CS_41)
Alert
Code Tll0
- Circuit
A Loss of Charge
This alert has "Service
Test" text that will be displayed
if the alert
occurred
during
service
test.
This
alert
occurs
when
the
compressor
is OFF and the suction
pressure
is less than 5 psig and
OAT
is greater
than
-5°F
for
I continuous
minute.
Use
the
Scrolling
Marquee
to reset
the
alert. The cause
of the
alert is
usually
low refrigerant
pressure
or a faulty
suction
pressure.
This
alert only
occurs
when
the compressor
is OFF because
the low
refrigerant
pressure
alarms (alert T133)
handle this situation
when
the compressor
is operating.
Alert
Code T126 - Circuit
A High Discharge
Pressure
This alert has
"Service
Test" text that will be displayed
if the alert
occurred
during
service test.
This alert occurs
when
alert T051 is
active while the appropriate condensing
temperature
is greater
than
150°F.
This
alert
reset
automatically.
The cause
of the
alert is
usually
an overcharged
system,
high outdoor
ambient
temperature
coupled
with
dirty
outdoor
coil, plugged
filter
drier, or a faulty
high-pressure
switch.
See Alert T051 for diagnostic
procedure.
Alert
Code T133 - Circuit
A Low Refrigerant
Pressure
This alert has "Service
Test" text that will be displayed
if the alert
occurred
during
service
test.
This
alert
occurs
when
the
compressor
is
operating
and
the
evaporating
temperature
(converted
from the suction
pressure)
is less than configured
low
suction
control
levels,
Configuration-+COOL-+SST-+SST.1
(Low
Suction
- Level
1) or SST.2
(Low
Suction
- Level
2) or
SST.3 (Low
Suction
Level 3). The circuit SST value
must be less
than SST.I
(for 5 nfinutes),
SST.2 (for 4 nfinutes),
or SST.3
(for 3
minutes
when
using
the economizer
and
1.5 minutes
when
not
using
the econonfizer)
for the alert to occur.
When
the outdoor
temperature
is less than 40°F, the above values are reduced
I°F for
every
2°F
the OAT is below
40°F.
An alert will also occur
if the
circuit
SST value
is less than SST.3
-5°F
for 20 seconds
and the
outdoor
temperature
is above 40°F.
All the above timers will reset
if the suction
temperature
rises above
SST.O
for I nfinute.
This
alert causes a strike for the respective
circuit.
This alert will activate
when
the coil becomes
frosted.
However,
during
the 15-nfinute
reset period,
the coils will thaw and strike should
clear and restart if
there
is nothing
else
wrong
with
the
circuit.
The
alert
resets
automatically.
The cause
of the
alert is usually
low
refrigerant
charge,
dirty filters,
evaporator
fan operating
backwards,
loose or
broken
belt, plugged
filter drier, faulty transducer,
excessively
cold
return air, or stuck open economizer
when the ambient
temperature
is low.
Alert
Code T143 - Circuit
A Failure
to Pressurize
This alert has "Service
Test" text that will be displayed
if the alert
occurred
during
service
test.
This
alert
occurs
when
the
compressor
turns
on
and
the
difference
between
suction
and
discharge
pressure
is less
then
the
Ckt A Minimum
Pressure
(Configuration-+COOL-+SST-+PSIJ)).
The pressure
difference
must be greater
then PSI.D
(default
is 20 psi) after 60 seconds
and
stay above
it while
running
the compressor.
This
alert causes
a
strike
for the respective
circuit.
The alert resets automatically.
The
cause
of the alert
is usually
compressor
wiring
causing
reverse
rotation
or a faulty compressor.
Alert
Code T153 - Real Time Clock Hardware
Failure
This
alert occurs
when
the RTC
clock
chip on the MBB
is not
responding.
Time and date functions
will not operate,
such as local
occupancy
schedules.
The unit will default
to 24/7
unoccupied
mode.
Recovery
is automatic
but MBB board replacement
may be
necessary.
Cycling
power
to the control
and reconfiguring
the time
and date should be tried before board replacement.
Alarm
Code A154
- Serial
EEPROM
Hardware
Failure
The unit will completely
shut down.
The serial EEPROM
chip on
the MBB, which
stores the unit's configuration,
is not responding.
26