Heating Modes - Carrier 50PD05 Operating And Service Instructions

Single package displacement ventilation or single zone variable airflow rooftop units electric cooling/gas heating with puron (r-410a) refrigerant and comfortlink 1.x controls
Hide thumbs Also See for 50PD05:
Table of Contents

Advertisement

Quality (IAQ) section of the Econonfizer Operation section above
for more details on Demand Control Ventilation (DCV).
Economizer Operation
for Units Equipped with Return Air
COy Sensor Only
When
the
CO 2
sensor
detects
a
CO 2
level or IAQ Level
(Inputs--+AIR.O--+IAO)
below
the
AQ
Differential
Low
(Configuration--,AIR.O--,AOD.L)
value
the MP.25,
MP.50,
MP.75 and MP.MX points will be recalculated to new values for
MP.25, MP.50, MP.75 based on the Econ Min IAQ Position
(Configuration--,AIR.O--,AO.MN).
The econonfizer outside air
damper will close and reduce the amount of outside air CFM to the
conditioned space based on the lower IAQ sensor readings and
indoor fan speed.
The econonfizer
outside air damper will
continue to close and reduce the amount of outside air CFM to the
conditioned space until the damper reaches user configurable Econ
Min IAQ Position (Configuration--,AIR.Q--,AQ_N).
This will
happen
when
the
Commanded
Fan
Speed
(Outputs-+FANS-+F.SPD)
is at the Supply Fan Maxinmm Speed
(Configuration--,UNIT--,FS_X).
When the Commanded
Fan
Speed
(Outputs-+FANS-+F.SPD)
is
between
Supply
Fan
Maximum
Speed
(Configuration---,UNIT---,FS_X)
and
the
Supply Fan Minimum Speed (Configuration---,UNIT---,FS_N)
the damper will operate in the shaded area of Figure 8 based on the
IAQ Level (Inputs-+AIR.Q-+IAQ).
Economizer
Operation
for Units Equipped
with Return Air
COy Sensor and outside air COy Sensor
The Econonfizer will operate sinfilar to Econonfizer Operation for
Units Equipped with Return Air CO2 Sensor Only but the IAQ
Level
(Inputs-+AIR.Q-+IAQ)
will
be deternfined
by
actual
outside air CO2 measurements instead of the 400 ppm CO2 default
value for OAQ.
Cooling
Mode Using
Space Temperature
Sensor
T55,
T56, T58 or T59 and Humidistat
(HL38MG029
or
TSTATCCPLH01-B)
Enhanced
dehunfidifying
will be provided
when a hunfidistat
(HL38MG029
or TSTATCCPLH01-B)
is connected the PD unit
ternfinal strip across the R and W2 ternfinals (since the PD unit
does not support the use of conventional thermostat inputs the W2
ternfinal is reconfigured for hunfidity input) and Space Hunfidity
Switch (Configuration--,UNIT--,RH.SW)
configuration
variable
is set to 1 (Normally
Open-no
call to dehunfidify).
Relative
hunfidity set point is set by adjusting the dial on the HL38MG029
or TSTATCCPLH01-B
device.
When the hunfidistat contacts
close and provide 24VAC to the W2 ternfinal the PD unit will reset
the Supply Air Control Point (Run Status---,COOL---,SA.CP)
by
one
degree
F
lower
than
the
Supply
Air
Set
Point
(Setpoint-+SASP)
or the current control point if the Supply Air
Set Point (Setpoint-+SASP)
has already been modified.
After 5
minutes if the humidistat contacts are still closed and 24 VAC is
being supplied to the W2 ternfinal the PD unit will reset the Supply
Air Control Point
(Run Status--+COOL--+SA.CP)
lower by one
more degree F. This reset cycle will continue to lower the supply
air temperature every 5 nfinutes until the Supply Air Control Point
(Run Status-+COOL-+SA.CP)
is equal to the Supply Air Set
Point
(Setpoint--+SASP)
+
SASP
Maximum
Reset
Down
(Configuration--+COOL-+SAT-+SA.MD).
The unit will continue
to operate at this reduced supply air temperature control point until
the hunfidistat contacts open and 24VAC is no longer supplied to
the W2 ternfinal. When 24VAC is no longer supplied to the W2
ternfinal the supply air control point will be reset higher by one
degree F. After 3 nfinutes if the hunfidistat contacts are still open
and 24VAC is not being supplied to the W2 ternfinal PD unit will
reset the Supply Air Control Point (Run Status---,COOL---,SA.CP)
higher by one more degree F. This reset cycle will continue to
raise the Supply Air Control Point (Run Status---,COOL---,SA.CP)
every 3 nfinutes until the Supply
Air Control
Point
(Run
Status--,COOL--,SA.CP)
is equal to the Supply Air Set Point
(Setpoint-+SASP)
or the supply air control point if reset was being
applied
due to cooling
requirements
that reset the Supply
Air Set
Point
(Setpoint-+SASP).
Whenever
Relative
Hunfidity
Reset
is
applied
the space temperature
is controlled
by modulating
the fan
speed even if the fan was locked
at 100% due to (Setpoint-+SASP)
reset.
Cooling Mode Using Space Temperature
Sensor T55,
T56,
or T58
and
Humidity Sensor (HL39ZZ007
or
33ZCSENRH-01)
Enhanced
dehumidifying
will be provided
when a humidly
sensor
(HL39ZZ007
or
33ZCSENRH-01)
4
to
20
ma
control
is
connected
the PD unit terminal strip across the TB1-J10
pin 3 and
4, power
to hunfidity
sensor
is connected
to R and C, the RH
Sensor
on OAQ
Input
(Configuration--,UNIT--,RH.S)
is set to
YES
and
Space
Hunfidity
Switch
(Configuration--,UNIT--,RH.SW)
configuration
variable
is set to
0.
Relative
hunfidity
set point
is set by changing
the value
of
Space
RH
Set point
(Setpoint--,RH.SP).
When
the
relative
hunfidity
in
the
space
is
above
the
Space
RH
Set
point
(Setpoint--,RH.SP)
the PD unit controls
will reset the supply
air
temperature
by one degree
F lower than the Supply
Air Set Point
(Setpoint--,SASP)
or the current
control
point
if the Supply
Air
Set Point
(Setpoint--,SASP)
has already
been modified.
After 5
nfinutes
the PD unit will reset the Supply
Air Control
Point
(Run
Status-+COOL-+SA.CP)
lower by one more degree F. This reset
cycle will continue
to lower the Supply
Air Control
Point
(Run
Status-+COOL-+SA.CP)
every
5 nfinutes
until the
Supply
Air
Control
Point
(Run
Status-+COOL-+SA.CP)
is equal
to the
Supply
Air Set Point (Setpoint--+SASP)
+ SASP
Maximum
Reset
Down
(Configuration--+COOL--+
SAT-+SA.MD).
When
the
relative
hunfidity
in the space
goes below the Space RH Set Point
(Setpoint-+RH.SP)
-
the
Space
RH
Deadband
(Setpoint--_RH.DB)
the
supply
air control
point
will
be
reset
higher
by one degree
F.
After 3 nfinutes
if the hunfidity
sensor
reading
is still below
the Space RH Set Point (Setpoint-+RH.SP)
-
the
Space
RH Deadband
(Setpoint--+RHJ)B),
the PD unit will
reset
the
Supply
Air
Control
Point
(Run
Status--+COOL--+SA.CP)
higher by one more degree F. This reset
cycle will continue
to raise the Supply
Air Control
Point
(Run
Status--+COOL--+SA.CP)
every
3 nfinutes
until
the
supply
air
temperature
control
point
is equal
to the Supply
Air
Set Point
(Setpoint--_SASP)
or the supply
air control point if reset was being
applied
due to cooling
requirements
that reset the Supply
Air Set
Point (Setpoint-+SASP).
Heating
Modes
Gas Heating
Mode
Using
Space
Temperature
Sensor
T55, T56,
or T58
(48PD Units Only)
For
gas
units,
the
Type
of
Heat
Installed
(Configuration---,HEAT---,HT.TY)
will be factory set to a value of
1.
Heat will not operate
if the outdoor
temperature
is greater
than the
value
configured
for
the
Heating
Lockout
Temperature
(Configuration---,HEAT---,HT_LO),
Heat
Mininmm
On
Time
(Configuration---,HEAT---,MRTJt)
and Heat Minimum
Off Time
(Configuration--+HEAT--,MOT.H).
Timeguards
apply
to both
stages of heating.
Factory
defaults
values are 2 nfinute s ON and 2
nfinutes
OFF.
The Integrated
Gas Controller
(IGC)
minimum
on-time
of 1 nfinute
will be followed
even if Heat Minimum
On
Time
(Configuration---,HEAT---,MRTJt)
is lower
and
during
Service Test.
If the indoor
fan control
is configured
to cycle with the heating
demand
by setting
Fan
ON When
Occupied
Heat
Minimum
On
Time
(Configuration--,UNIT--,OC.FN)
to NO, the fan will stop
after
a
delay
configured
by
Fan-off
Delay,
Gas
Heat
(Configuration-+HEAT-+FOD.G).
The
factory
default
for
Fan-off
Delay,
Gas Heat (Configuration--+HEAT--+FOD.G)
is 45
seconds.
If the
IGC temperature
limit switch
opens
within
10
nfinutes
of the end of the gas heat cycle, the next fan off delay will
2O