Carrier 50PD05 Operating And Service Instructions page 94

Single package displacement ventilation or single zone variable airflow rooftop units electric cooling/gas heating with puron (r-410a) refrigerant and comfortlink 1.x controls
Hide thumbs Also See for 50PD05:
Table of Contents

Advertisement

AIRFLOW
(Cfm)
1200
1300
1400
1500
1600
1700
1800
1900
2000
Table 50 -- Fan Performance
- 48PDD05
Horizontal
Units
AVAILABLE EXTERNAL STATIC PRESSURE
(in. wg)
0.2
0.4
Rpm
Bhp
Rpm
Bhp
Rpm
436
0.12
559
0.19
661
456
0.14
574
0.22
673
477
0.17
592
0.25
687
500
0.20
611
0.29
703
523
0.24
631
0.33
721
548
0.28
652
0.38
739
573
0.32
674
0.43
759
600
0.37
697
0.48
779
627
0.43
720
0.55
801
0.6
Bhp
0.27
0.30
0.34
0.38
0.43
0.48
0.54
0.60
0.67
Rpm
753
762
774
787
801
818
835
854
873
0.8
1.0
Bhp
Rpm
Bhp
0.35
839
0.45
0.39
845
0.49
0.43
853
0.53
0.48
864
0.58
0.53
877
0.63
0.58
891
0.69
0.64
906
0.76
0.71
923
0.83
0.79
941
0.91
AIRFLOW
1.2
(Cfm)
Rpm
Bhp
1200
918
0.54
1300
922
0.58
1400
929
0.63
1500
937
0.69
1600
947
0.74
1700
959
0.81
1800
973
0.88
1900
988
0.95
2000
1004
1.04
LEGEND
Bhp
- Brake Horsepower
High Range Motor/Drive
Required
AVAILABLE EXTERNAL STATIC PRESSURE
(in. wg)
1.4
1.6
Rpm
Bhp
Rpm
Bhp
Rpm
993
0.64
1063
0.75
1130
995
0.69
1064
0.80
1130
1000
0.74
1067
0.85
1132
1006
0.80
1072
0.91
1136
1015
0.86
1079
0.98
1141
1025
0.93
1088
1.05
1148
1037
1.00
1098
1.13
1157
1050
1.08
1110
1.21
1168
1065
1.17
1123
1.30
1179
NOTES:
i. Maxinmnl continuous
BHP is 2.0.
2. See General Fan Performance
Notes.
1.8
Bhp
0.86
0.91
0.97
1.03
1.10
1.18
1.26
1.35
1.44
AIRFLOW
(Cfm)
1200
1300
1400
1500
1600
1700
1800
1900
2000
Table
51 -- Fan Performance
- 48PDE05
Horizontal
Units
AVAILABLE EXTERNAL STATIC PRESSURE
(in. wg)
0.2
0.4
Rpm
Bhp
Rpm
Bhp
Rpm
443
0.12
564
0.20
666
463
0.15
580
0.22
678
485
0.17
598
0.26
693
508
0.21
617
0.30
709
532
0.24
638
0.34
727
558
0.28
660
0.39
746
584
0.33
682
0.44
766
611
0.38
706
0.50
788
639
0.44
731
0.56
810
0.6
Bhp
0.27
0.31
0.34
0.39
0.43
0.49
0.55
0.61
0.68
Rpm
758
767
778
792
8O7
824
842
861
882
0.8
2.0
Rpm
Bhp
1193
0.97
1193
1.03
1194
1.09
1196
1.16
1201
1.23
1207
1.31
1214
1.39
1223
1.48
1234
1.58
AVAILABLE EXTERNAL STATIC PRESSURE
(in. wg)
AIRFLOW
1.2
1.4
1.6
(Cfm)
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
1200
922
0.55
996
0.65
1066
0.75
1133
1300
926
0.59
999
0.69
1068
0.80
1133
1400
933
0.64
1004
0.75
1071
0.86
1136
1500
942
0.69
1011
0.80
1077
0.92
1140
1600
952
0.75
1020
0.87
1084
0.99
1146
1700
965
0.82
1030
0.94
1093
1.06
1153
1800
979
0.89
1043
1.01
1104
1.14
1163
1900
995
0.97
1057
1.09
1116
1.22
1174
2000
1012
1.05
1072
1.18
1130
1.32
1186
LEGEND
NOTES:
Bhp - Brake Horsepower
i. Maxinmnl continuous BHP is 2.0.
2. See General Fan Per_rmanee Notes.
High Range Motor/Drive
Required
1.8
1.0
Bhp
Rpm
Bhp
0.36
842
0.45
0.40
849
0.49
0.44
858
0.54
0.48
869
0.59
0.54
882
0.64
0.59
896
0.70
0.66
912
0.77
0.72
930
0.84
0.80
948
0.92
Bhp
0.86
0.92
0.98
1.04
1.11
1.19
1.27
1.36
1.46
2.0
Rpm
Bhp
1196
0.97
1196
1.03
1197
1.10
1200
1.17
1205
1.24
1211
1.32
1220
1.41
1229
1.50
1240
1.60
94

Advertisement

Table of Contents
loading

This manual is also suitable for:

48pd0550pd0648pd06

Table of Contents