Carrier 50PD05 Operating And Service Instructions page 84

Single package displacement ventilation or single zone variable airflow rooftop units electric cooling/gas heating with puron (r-410a) refrigerant and comfortlink 1.x controls
Hide thumbs Also See for 50PD05:
Table of Contents

Advertisement

APPENDIX
B - VFD INFORMATION
(CONT)
To adjust
the speed
in HAND
mode,
press
the UP or DOWN
buttons
(the reference
changes
immediately).
The reference
can be
modified
in
the
local
control
(HAND)
mode,
and
can
be
parameterized
(using
Group
11 reference
select)
to also
allow
modification
in the remote
control
mode.
Parameters
Mode
The Parameters
mode
is used to change
the parameters
on the
drive. To change parameters,
perform
the following
procedure:
1. Select
MENU
(SOFT
KEY
2). The
Main
menu
will be
displayed.
2. Use the UP or DOWN
keys to highlight
PARAMETERS
on the display
screen and press ENTER
(SOFT
KEY 2).
3. Use
the
UP
or DOWN
keys
to highlight
the
desired
parameter
group
and press SEL (SOFT
KEY 2).
4. Use
the
UP
or DOWN
keys
to highlight
the
desired
parameter
and press EDIT (SOFT
KEY 2).
5. Use the UP or DOWN
keys
to change
the value
of the
parameter.
6. Press
SAVE (SOFT
KEY
2) to store
the modified
value.
Press CANCEL
(SOFT
KEY 1) to keep the previous
value.
Any modifications
that are not saved will not be changed.
7. Choose
another
parameter
or press EXIT (SOFT
KEY 1) to
return to the listing
of parameter
groups.
Continue
until all
the parameters
have been configured
and then press EXIT
(SOFT
KEY 1) to return to the main menu.
IMPORTANT:
The current
parameter
value
appears
above the
highlight
parameter.
To view the default
parameter
value, press the
UP and DOWN
keys sinmltaneously.
To restore the default
factory
settings,
select the Carrier application
macro.
Start-Up
Assistant
Mode
To use the Start-Up
Assistant,
perform
the following
procedure:
1. Select
MENU
(SOFT
KEY
2).
The Main menu
will be
displayed.
2. Use the UP or DOWN
keys to highlight
ASSISTANTS
on the display
screen and press ENTER
(SOFT
KEY 2).
3. Use the UP or DOWN
keys to highlight
Commission
Drive and press SEL (SOFT
KEY 2).
4. The Start-Up
Assistant
will display the parameters
that need
to be configured.
Select the desired
values
and press SAVE
(SOFT
KEY
2) after
every
change.
The
process
will
continue
until all the parameters
are set. The assistant checks
to make sure that entered
values are in range.
The assistant
is divided
into separate
tasks.
The user can activate
the
tasks
one
after
the
other
or independently.
The
tasks
are
typically
done
in this order:
Application,
References
1 and
2,
Start/Stop
Control,
Protections,
Constant
Speeds,
PID
Control,
Low Noise Setup, Panel Display,
Timed
Functions,
and Outputs.
Changed
Parameters
Mode
The ('hanged
Parameters
mode
is used to view
and edit recently
changed
parameters
on the drive. To view the changed
parameters,
perform
the following
procedure:
1. Select
MENU
(SOFT
KEY
2). The
Main
menu
will be
displayed.
2. Use the UP or DOWN
keys to highlight
CHANGED
PAR
on the display
screen
and press ENTER
(SOFT
KEY
2). A
list of the recently
changed
parameters
will be displayed.
3. Use
the
UP
or DOWN
keys
to highlight
the
desired
parameter
group
and press EDIT (SOFT
KEY 2) to change
the parameter
if desired.
4. Press EXIT (SOFT
KEY 1) to exit the Changed
Parameters
mode.
Drive
Parameter
Backup
Mode
The drive parameter
back up mode
is used to export
the parameters
from one drive to another. The parameters
can be uploaded
from a
VFD to the removable
control
panel. The control
panel can then be
transferred
to another drive
and the parameters
downloaded
into
memory.
Depending
on the motor
and application,
there
are two
options
available.
The first
option
is to download
all parameters.
This
copies both application
and motor parameters
to the drive from the
control
panel.
This
is
recommended
when
using
the
same
application
for drives
of the same
size. This can also be used to
create a backup
of the parameters
group for the drive.
The second
option
downloads
only
the application
parameters
to
the drive. This is recommended
when
using the same application
for drives
of different
sizes.
Parameters
9905,
9906,
9907,
9908,
9909,
1605,
1607,
5201,
and group
51 parameters
and internal
motor parameters
are not copied.
Upload
All Parameters
To upload
and store parameters
in the control
panel from the VFD,
perform
the following
procedure:
1. Select
MENU
(SOFT
KEY
2). The Main
menu
will be
displayed.
2. Use the UP or DOWN
keys to highlight
PAR BACKUP
on
the display
screen and press ENTER
(SOFT
KEY 2).
3. Use the UP or DOWN
keys to highlight
UPLOAD
TO
PANEL
and press SEL (SOFT
KEY 2).
4. The text "Copying
Parameters"
will be displayed
with
a
progress
indicator.
To stop
the
process,
select
ABORT
(SOFT
KEY 1).
5. When
the upload
is complete,
the text "Parameter upload
successful"
will be displayed.
6. The display
will then return
to the PAR BACKUP
menu.
Select EXIT (SOFT
KEY 1) to return to the main menu.
7. The control
panel can now be disconnected
from the drive.
Download
All Parameters
To download
all parameters
from
the control
panel
to the VFD,
perform
the following
procedure:
1. Install the control
panel with the correct parameters
onto the
VFD.
2. Select
MENU
(SOFT
KEY
2). The Main
menu
will be
displayed.
3. Use the UP or DOWN
keys to highlight
PAR BACKUP
on
the display
screen and press ENTER
(SOFT
KEY 2).
4. Use the UP or DOWN
keys to highlight
DOWNLOAD
TO
DRIVE
ALL
and press SEL (SOFT
KEY 2).
5. The text "Restoring
Parameters"
will be displayed
with
a
progress
indicator.
To stop
the
process,
select
ABORT
(SOFT
KEY 1).
6. When
the
download
is complete,
the
text
"Parameter
download
successful"
will be displayed.
7. The display
will then return
to the PAR BACKUP
menu.
Select EXIT (SOFT
KEY 1) to return to the main menu.
8. The control
panel can now be disconnected
from the drive.