Compressor Operation; Indoor Fan Operation - Carrier 50PD05 Operating And Service Instructions

Single package displacement ventilation or single zone variable airflow rooftop units electric cooling/gas heating with puron (r-410a) refrigerant and comfortlink 1.x controls
Hide thumbs Also See for 50PD05:
Table of Contents

Advertisement

(Configuration--+CCN--+SCH.O--+OV.SP)
is set to YES.
The length
of the override
period
is detemfined
by the
Timed
Override
Hours
setting
(Con figuration--+CCN--+
SCH.O--+O
V>EX).
Compressor
Operation
The 48/50 PD units use a Copeland
Digital
Scroll Compressor
that
can vary
the refrigerant
capacity
between
100 and 15%.
This
is
accomplished
by a mechanism
in the compressor
that separates
the
two scroll
spirals
which
stops the pumping
of the refrigerant
gas.
This mechanism
is operated
by the differential
pressure
between
the suction
and discharge
of the compressor.
The pressure
to
operate
the unloading
mechanism
is controlled
by a small solenoid
situated
in a refrigerant
line between
the top of the compressor
and
the suction
line.
When the solenoid
is energized
the compressor
is
unloaded.
The solenoid
coil is controlled
by the Copeland
Digital
Scroll Controller
(DSC)
that operates
on a 1 to 5V signal from the
ComfortLink
Auxiliary
Board
(AUXI)
and converts
this into
a
Pulse Width
Modulated
(PWM)
signal to the solenoid
valve.
The
pulse width
modulated
signal is an on and off signal that repeats
every
15 seconds
with
the
off time
portion
of the
15 seconds
representing
the % loading
of the compressor.
The
Compressor
Capacity
(Outputs--+COOL--+CAPC)
can
be
monitored
on the ComfortLink
Scrolling
Marquee
Display.
The
Compressor
Capacity
value
is detemfined
by
a Proportional,
Integral,
Derivative
(PID)
algorithm
that controls
the Supply
Air
Temperature
(Temperatures--+AIR.T--+SAT)
to the
Supply
Air
Control
Point (Run
Status--+COOL--+SA.CP).
The
Compressor
Minimum
Capacity
(Configuration---,COOL---,MIN.C)
is configured
at the factory
to
70%.
This
is the minimum
compressor
capacity
that
gives the
highest
SEER rating
for a 48 series unit with
the highest
gas heat
option
and no economizer
per AHRI
standard
210/240.
Since the
AHRI rating standard
does not account
for energy savings
that can
be realized
by displacement
ventilation
air distribution
system
and
extending
economizer
cooling
operation
at higher
supply
air
temperature
set points,
a complete
energy
analysis
should
be
conducted
before
changing
the Compressor
Minimum
Capacity
(Configuration---,COOL---,MIN.C)
setting to detemfine
the energy
savings
at
a
lower
Compressor
Minimum
Capacity
(Configuration--,COOL--,MIN.C)
setting.
Indoor
Fan Operation
The indoor
fan is controlled
by the Indoor
Fan VFD Power
Relay
(Outputs_FANS_IDF)
on the MBB
(main base board)
control,
which
then
operates
the
indoor
fan contactor
(IFC).
On the
48/50PD
units
the
Indoor
Fan
VFD
Power
Relay
(Outputs---,FANS---,IDF)
is always
on so that power is supplied
to
the
VFD
electronic
boards.
This
prevents
the
formation
of
condensation
on the VFD electronic
boards
and provides
power to
the remote
VFD display
so that error codes and VFD configuration
parameters
can be verified.
The 48/50PD
unit controls
require
an accurate
supply duct CFM at
the unit design
point where
the indoor
fan will run at the Supply
Fan
Maxinmm
Speed
(Configuration-_UNIT--,FS_X).
The
Supply
Fan Maximum
Speed
(Configuration--_UNIT--_FS_X)
is used for operation
of the economizer
and power exhaust.
The
supply
duct CFM is configured
by the Indoor
Fan Max
Speed
CFM
(Configuration-_ECON-_IDF.C).
Default
values
for
Indoor
Fan Max Speed
CFM
(Configuration-_ECON-_IDF.C)
are at 400
CFM per ton or 1600
CFM for the 05 size and 2000
CFM for the 06 size.
It is preferred
to use the supply
duct CFM
from an air balance
report to configure
the Indoor Fan Max Speed
CFM (Configuration--+ECON--+IDF.C).
If an air balance
report
is not available
then use the fan tables
supplied
in this book
to
deternfine
Fan
Max
Speed
CFM
(Configuration---,ECON---,IDF.C).
When using
the fan tables to
deternfine
Fan
Max
Speed
CFM
(Configuration---,ECON---,IDF.C)
set Economizer
Position
Test
(Service
Test--+INDP--+ECON)
to 0 (Econonfizer
Damper
Closed)
and Indoor Fan Speed Test (Service
Tes---,FANS---,F.SPD)
equal to
(Configuration---,UNIT---,FS.MX).
Measure
the supply
to return
duct
static
pressure
difference
and
indoor
fan
RPM.
Make
correction
to static pressure
for all options
installed
in the unit per
the
accessory
pressure
drop table.
Deternfine
Indoor
Fan
Max
Speed
CFM
(Configuration---,ECON---,IDF.C)
on the fan table
where the corrected
static pressure
and RPM cross.
The
supply
fan speed
range
is configured
by the
Supply
Fan
Maximum
Speed
(Configuration---,UNIT---,FS_X)
and
the
Supply
Fan Minimum
Speed
(Configuration---,UNIT---,FS.MN).
These configuration
values
are in units
of % speed referenced
to a
2 to 10VDC
signal to the VFD AI1 input with 2VDC
representing
0%
speed
and 10VDC
representing
100%
speed
or 0 to 60HZ
VFD frequency
output to the motor.
The
Supply
Fan
Minimum
Speed
(Configuration---,UNIT---,FS.MN)
can
be
user
configured
between
10 and 70%.
The Supply
Fan Minimum
Speed
default
value is 70%, this provides
the greatest
energy efficiency
rating for
a unit without
an economizer
in a mixed
air type duct application.
The
Supply
Fan
Maximum
Speed
(Configuration---,UNIT---,FS.MX)
can be configured
between
80
and 100%.
The Supply
Fan
Maximum
Speed
default
value
is
100%.
Set the indoor
fan pulley
to the application
design
point
CFM for heating
and cooling
at 100% fan speed so that the CFM is
not lower than the minimum
CFM allowed
in the product
data.
If
the exact CFM can not be set by the half turn pulley
settings
then
adjust
the
Supply
Fan
Maximum
Speed
(Configuration---_UNIT---_FS_X)
to fine tune
the
CFM
to the
application
requirements,
The
Supply
Fan
Maxinmm
Speed
(Configuration---_UNIT--_FS_X)
RPM
nmst
now
produce
supply
CFM that is not lower that the nfinimum
CFM allowed
in
the product
data for heating
and cooling,
The
indoor
fan may
operate
during
cooling
with
compressors
mode,
free cooling
with
outdoor
air mode,
heating
mode,
or for
ventilation
with outdoor
air mode,
The indoor
fan operation
can be affected
by the following:
• Fan On When Occupied
(Configuration--+UNIT--+OC.FN)
• IAQ Analog
Fan Config
(Configuration--+AIR.Q--+IA.FN)
• IAQ Switch Fan Config
(Configuration--+AIR.Q--+ILFN)
• Fan Status Switch
(Configuration---,UNIT---,FN.SW)
When
the unit
is in occupied
or unoccupied
cooling
mode
the
supply
fan will modulate
to maintain
the space
temperature
sensor
set point
between
the configured
Supply
Fan
Maximum
Speed
(Configuration---,UNIT---,FS_X)
and the Supply
Fan Minimum
Speed (Configuration--+UNIT--+FS.MN).
When
the
40PD
or 50 PD unit
is in occupied
or unoccupied
heating
mode
(gas heat or electric
heat mode)
the indoor
fan will
operate
at
the
Supply
Fan
Maximum
Speed
(Configuration--_UNIT--_FS_X)
setting.
For 48PD
gas heating
units,
the IGC control
fan output
is also
monitored
by the
MBB
control.
This
can result
in additional
modifications
of fan delays
or other
operation
due
to safety
functions
of the IGC control.
When
the PD unit is in free cooling
mode
the indoor
fan will
modulate
to
maintain
The
Occupied
Cool
Set
Point
(Setpoints-,OCSP),
the
Unoccupied
Cool
Set
Point
(Setpoints---,UCSP),
Occupied
Heat
Set
Point
(Setpoints---,OHSP),
or
the
Unoccupied
Heat
Set
Point
(S etpoints---, UHSP) .
When
the PD
unit is in ventilation
mode
and
Fan
On
When
Occupied
(Configuration---,UNIT---,OC.FN)
the indoor
fan will
operate
at
the
Vent
Mode
Fan
Speed
(Configuration---,UNIT---,FS.VM).
Vent
Mode
Fan
Speed
(Configuration---,UNIT---,FS.VM)
factory default
is 50% and can
be user configured
between
40 and 100%.